TECHNICAL SPECIFICATIONS 

Operating Voltage Range

9 - 

30

 VDC

 (Nom. 12/24VDC)

Average c

urrent consumption

 in quiescent state . . .

< 5

0

µ

A

Alarm state current: . . . . . . . . . . . . . . . . . . . . . . . . . 18

 mA

 / 9V;

                                                                                    29mA / 12V; 
                                                                                    32mA/ 15V
Class (in accordance with EN54-5)

. . . . . . . . . . . . .

A1/R

Protected area (in accordance with EN54-5)

. . . . . .

up 

35m²

 

Installation height

 

(in accordance with EN54-5)

. . . .

up 

3

,5

m

Output in alarm state at terminal RI

. . . . . . . . . . . . .

20mA (max)/ -3.3V

(Towards terIN /+OUT/)

Degree of protection

. . . . . . . . . . . . . . . . . . . . . . . . .

IP30

2

2

Wire Gauge for terminals . . . . . . . . . . . . . . . . . . . . . 0.4mm

 

ё

 2.0mm

 

Operational temperature range

. . . . . . . . . . . . . . . . .

-1

0

C

 

ё

 +6

0

C

Relative humidity resistance

. . . . . . . . . . . . . . . . . . .

(93

 ± 3)%

 @

 40

C

Dimensions (incl. base)

. . . . . . . . . . . . . . . . . . . . . .

ø102mm, h 42mm

Weight (incl. base)

. . . . . . . . . . . . . . . . . . . . . . . . . .

160g

. . . . . . . . . . . . . . . . . . . . .

°

°

°

ATTENTION:

 This manual is subject to change without  notice

!

 

Read carefully this installation instructions before installing the device!

1

293-CPD-0118

RHD212

RATE-OF-RISE TEMPERATURE 
DETECTOR WITH RELAY BASE

Installation Manual No: 18020746

GENERAL DESCRIPTION:

The 

RHD212

 is a special kit for using in intruder alarm systems. The kit includes the 

rate-of-rise temperature fire detector

 RHD-2

 and relay base 

DB-12L/U 

(12V)

.

INSTALLATION
1. Choose the proper place for installation

 of the fire detector. Refer to the given 

installation instructions. 

Note:

 

Do not   install the detector near to natural heat sources, e.g. above cookers, 

ovens or fire places.

2. If you want to “lock” the detector to the base

 remove the little “tooth” (with the 

triangle shape) and break the plastic key off the base. Keep the plastic key in safe place 
to be able to open the detector later.

3.  Mount  the  relay  base

  on  the  ceiling  of  the  protected  premises  using  fixings

 

according the mounting surface.

4.  Connect the detector base

 to the intruder alarm  panel using the wiring diagram. 

ATTENTION: 

 Disconnect the main power supply  before installing the detector!

5. Insert the detector into the base 

and rotate clockwise until it drops into place. 

Continue to rotate the detector until it locks to the base  -  a click is heard.

6. If the detector has been locked

 

to the base,

 

when open it

 for a service schedule 

maintenance and cleaning you have to use the plastic key. Light press with the plastic 
key

 

into the base opening and at the same time rotate the detector head counter-

clockwise.

ATTENTION:

 To clean the wire mesh you have to remove the detector’s PCB and 

then carefully to disassemble the smoke chamber from it. Clean the wire mesh 
and mount the chamber back on the PCB as observe the arrows - they have to 
coincide, then slightly press the chamber to the detector’s PCB. Next you have 
to mount the PCB back to detector’s plastic body. Find the color dot sticker on 
the  PCB  and  orientate  it  to  the  mark  on  the  plastic  body  (visible  from  the 
outside). The hole next to the color dot have to coincide with the pin on the 
plastic body. Gently press downwards to fix the PCB in place.

TESTING THE DETECTOR
To test the detector use a smoke probe:

1. Apply power to the detector.
2. Wait  for 30 sec.
3. Apply the heat tester (

Cordless Heat Detector Tester or Heat Tester 110V>240V

) at 

a distance 20cm to test the heat part of the detector. Within 8 sec the fire detector will 
enter in fire condition. Both LEDs will light up.
4. Power off the detector for 2sec minimum.  After resetting the detector will enter in 
duty mode and the LEDs will light off.

SERVICE MAINTENANCE

1. Inspection for visible physical damage - weekly.
2. Operational test in real conditions - monthly.
3. Check and clean dust contamination - six months.
4. Check and clean base and head contacts and connections - annually.