MAGPRO-WS

Intelligent analogue addressable 

fire alarm sounder MAGPRO-

WS

Distributor:

 Elite Security Products Ltd, 

Unit 7 Target Park, Shawbank Road

 

Lakeside, Redditch B98 8YN, UK

http://www.espuk.com

Manufacturer: 

Teletek Electronics JSC

Address: 14A Srebarna Str, 1407 Sofia, Bulgaria

Http://www.teletek-electronics.com

Installation Instruction

MAGPRO-WS is аn addressable Wall Mount Sounder designed for installing in addressable fire alarm systems supporting MAGPRO 
communication protocol. The device is powered on from the panel and can be controlled via the communication protocol.

The device SensoIRIS WS is compatible with fire base MAGPRO-DB  

for ceiling or wall mounting and WSB IP65 for wall mounting

Attention

Power off the loop circuit

 

before installing the MAGPRO-WS addressable fire base

!

1. Choose the proper place for installation of the device

.

2. Set the device address 

using

 

MAGPRO-PROG

 Programmer

 or directly from addressable fire panel

The address must be in the range from

 

to

 250.

 

3. Mount the fire base

 on the ceiling or on the wall of the protected premises using fixings

 

according the mounting surface.

4. Connect the base

 to the fire panel using the wiring diagram. 

5. Insert the sounder into the base 

and rotate clockwise until it drops into place - the short mark on the base fits with that on the sounder body. 

Continue to rotate the sounder until its mark coincides with the long mark on the base  -  a click is heard.

6. Program the device parameters. 

Choose in consecutiveness from the control panel: 

System - Programming - Devices - Loop. 

Find the 

installed sounder, as enter address, loop and zone number - the panel automatically will recognize the type of the device. Choose the button 

MORE

  to enter in the additional settings menu. 

7. Test the sounder for proper operation.

TECHNICAL SPECIFICATIONS 

18020180; RevC; 01/2018

!

A-weighted sound 
level 

diagram

ATTENTION: Read carefully this installation Instructions before installing 
the device!

This manual is subject to change without  notice

!

91dB

9

6

dB

95dB

90dB

86dB

1m

86dB

15°

45°

75°

105°

135°

165°

EN54-3:2001

EN54-3:2001/A1:2002
EN54-3:2001/A2:2006

Sounder Type B

DoP No: 040

1293-CPR-0463 Rev.1

1293

17

Operating Voltage Range . . . . . . . . . . . . . . . . . . 15

 - 

3

2VDC

 (Nom. 27VDC)

Nominal consumption (stand-by) . . . . . . . . . . . .

<500

μ

А@27

VDC

Maximal consumption (main tone type 27)

:

     - 

low volume level. . . . . . . . . . . . . . . . . . . . . .

<

5m

А

     - high volume level . . . . . . . . . . . . . . . . . . . . .

<

16.5m

А

Maximal consumption (other tone types):

     - 

low volume level. . . . . . . . . . . . . . . . . . . . . .

<4

m

А

     - high volume level . . . . . . . . . . . . . . . . . . . . .

<

1

0

m

А

Power volume (main tone type 27)

:

     - low volume . . . . . . . . . . . . . . . . . . . . . . . . . . ~ 80dB

 

(A) 

± 

6dB @ 1m

     - high volume . . . . . . . . . . . . . . . . . . . . . . . . . ~ 92dB

 

(A) 

± 5

dB @ 1m

Power volume (other tone types)

:

     - 

low volume . . . . . . . . . . . . . . . . . . . . . . . . . . 75-85dB 

± 

3dB @ 1m

     - high volume . . . . . . . . . . . . . . . . . . . . . . . . . 80-95dB 

± 

3dB @ 1m

Number of tone types . . . . . . . . . . . . . . . . . . . . .

32

Supported communication protocol. . . . . . . . . . . MAGPRO

2

Wire Gauge for terminals . . . . . . . . . . . . . . . . . . 2.5mm

 

Relative humidity resistance

. . . . . . . . . . . . . . . .

(93

 ± 3)%

 @

 40°

C

Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116x55mm
Color

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

red

Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ABS

Essential characteristics

Performance under fire 
conditions

Performance

Operational reliability

Pass

Pass

Temperature resistance

Humidity resistance

Corrosion resistance

Resistance to ingress

Electrical stability

Shock and vibration
resistance

Durability:

Pass

Pass

Pass

Pass

Pass

Pass

 -10°C 

÷

 +

50

°C

Installation

~183

g

Indoor use*

Outdoor use**

!

IP43C (ЕN54-3)*

IP65 (EN60529)**

* When used with base MAGPRO-DB
** When used with base WSB IP65