Installation Instructions

MAGPRO-HD1

Intelligent analogue addressable fire 

alarm heat detector

Distributor:

 Elite Security Products Ltd, 

Unit 7 Target Park, Shawbank Road

 

Lakeside, Redditch B98 8YN, UK

http://www.espuk.com

Manufacturer: 

Teletek Electronics JSC

14A Srebarna Str, 1407 Sofia, Bulgaria

EN 54-5: 2000/ A1: 2002,

Detector Class A1/R, A2/S, B/S

DoP No: 038

Tested by EVPU: N.B.1293

1293

15

ATTENTION:

 

Read carefully this installation instruction before installing the device. 

This manual is subject to change without notice errors and omissions accepted.

>30cm

>30cm

<7m 

 

- MAGPRO-HSD1

<5m 

-

 

   MAGPRO-SD1

MAGPRO-HD1

,  

18020163, RevB, 02/ 2015

GENERAL DESCRIPTION:

MAGPRO-HD1 is 

а

n addressable temperature detector designed for use with ESP MAGPRO fire alarm panels. The detector is powered from 

the panel and can be controlled via its communication protocol.
The MAGPRO-HD1 is compatible with detector base MAGPRO-DB.

INSTALLATION
1. 

Select a suitable position for installation. 

Note: Do not install the detector near to natural heat sources, e.g. above cookers, ovens or fire 

places.

 

2. 

Mount the detector base to the required surface with suitable fixings.

3. 

Connect the detector base to the fire panel using the wiring diagram. 

ATTENTION: Disconnect the loop power before installing the detector!
4.

 To activate the anti tamper lock option on the detector base carefully remove the small tooth shown in Fig2 using short nose snips.

5.

 To locate the detector onto the base align the line mark on the detector with the short line mark on the detector base. Rotate the detector  

clockwise until the short line mark on the detector coincides with the long mark on the base and a “click” is heard.

6.

 If removal of the detector is required after the detectors anti tamper lock function has been selected a small flat blade screwdriver should be 

inserted into the aperture on the side of the detector base. Lightly press with the screwdriver at the same time as rotating the detector head in 
a counter-clockwise direction.

TECHNICAL SPECIFICATIONS 

Operating Voltage Range . . . . . . . . . . . . . . . . . . . . . . . 15

 - 

32

VDC

 (Nom. 27VDC)

C

onsumption

 in quiescent state, no communication . . < 130

μ

A@27VDC

C

onsumption

 in quiescent state, with communication

.

< 1

8

0

μ

A@27VDC 

Consumption in alarm state, with communication . . . . 6.5mA
Class

selectable from the control panel

. . . . . . . . . . .

A1/R, A2/S, B/S

Protected area (in accordance with EN54-5)

. . . . . . . .

up 

35m²

Installation height

 

(in accordance with EN54-5)

. . . . . .

up 

3

,5

m

Output in alarm state at terminal RI (terminals 4/ 1)

. . .

7.5 mA (max)/ 7.5V

2

2

Wire Gauge for terminals . . . . . . . . . . . . . . . . . . . . . . . 0.4mm

 

ё

 2.0mm

 

Relative humidity resistance

. . . . . . . . . . . . . . . . . . . . .

(93

 ± 3)%

 @

 40°

C

Dimensions (incl. base)

. . . . . . . . . . . . . . . . . . . . . . . .

ø103mm, h 42mm

Essential characteristics 

Performance 

Performance under fire conditions 

Pass 

Operational reliability 

Pass 

Durability of  operational reliability and response delay: temperature resistance 

Pass 

Durability of  operational reliability: humidity resistance 

Pass 

Durability of  operational reliability: shock and vibration resistance 

Pass 

Durability of  operational reliability: corrosion resistance 

Pass 

Durability of  operational reliability: resistance to ingress 

Pass 

 

IP30

 -10°C 

÷

 +

60

°C

Installation

~

1

10

g

Indoor

Outdoor

!

Without base