EsiWelma Sensigas URS20SI Quick Start Manual Download Page 6

EsiWelma Srl

 

URS20SI_en.doc - rev. 0 

Oxygen detectors – URS20SI 

20/10/2010 

Gas detection systems for industrial environments 

6/8

 

 

Electrical installation of 
the optional relay card 

Selecting the type of 
contact on the terminal 
board: 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Configuring the relay 
operating mode:

 

After mechanically installing the relay card, it is necessary to configure it electrically, 
selecting the relay operating mode and the type of contact desired on the terminal 
board (NC or NO). 

A pair of extractable terminals is available for each relay; the type of contact (NC or 
NO) to be associated with them can be selected using the 

JP1…JP4

 jumpers. 

 
NC or NO contact of pre-alarm relay 
NC or NO contact of 1

st

 THRESHOLD relay 

NC or NO contact of 2

nd

 THRESHOLD relay 

NC or NO contact of FAIL relay 

 

DL1 (yellow),   Sensor FAIL 

DL2 (red),  2

nd

 alarm THRESHOLD 

DL3 (red),  1

st

 alarm THRESHOLD

 

DL4 (red),   Pre-alarm  

 
Selecting the terminal contact: 
 
 
 

NC                         NO 

 
 
 
To set the operating mode of the relays: for direct (relay energised by event) or 
reverse (relay energised with no event), it is necessary to use the 6th selector of the 
DIP switch at 

S1

; in particular: 

 
 

                                              direct operating mode  

reverse operating mode 

 

Checklist after 
mechanical and 
electrical installation 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

The sensors are factory calibrated so they normally do not require any other 
calibration once installed. Still, after installation, an operational check of the sensors 
is recommended. 
The detector will enter a 2-minute warm-up phase after power-up. 
After this time, the sensor will switch to normal operating mode, but it will take about 
2 hours before it reaches top performance level. 
When the detector is operating, a gas response check should be carried out using 
the 

TUL40..

 gas calibration kit. This kit contains: 

1 calibration gas cylinder: 4% of O

2

; (see kit part numbers on the specific 

technical data sheet) 

pressure valve and flow regulator 

sensor body adapter 

about 2 metres of hose between cylinder and adapter. 

During the test, check the output current, the status of the LED visible on the 
outside of the enclosure and, if present, the status of the LEDs on the relay card 
before closing the housing 

The LED on the housing and the 4...20mA output have the following operating 
meaning: 

Sensor status 

4...20mA Output

Status LED on housing 

WARM-UP 

2mA 

Flashing at 2Hz frequency 

OPERATING 

1 flash about every 10 sec. 

PRE-ALARM 

2 flashes about every 5 sec. 

1

st

 ALARM THRESHOLD 

3 flashes about every 5 sec. 

2

nd

 ALARM THRESHOLD 

4...20mA 

0,10,20mA for 

threshold 

applications 

4 flashes about every 5 sec. 

SENSOR FAIL 

22mA 

Steady 

  D   |   

  B   |   

1   2   3   4   5   6   7   8 

ON 

1   2   3   4   5   6   7   8 

ON 

Summary of Contents for Sensigas URS20SI

Page 1: ...nd more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SI sensors can be...

Page 2: ...thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up to 200 at 1...

Page 3: ...rs must be located at the breathing height of the occupants in the premises Take into consideration the following specific installation guidelines as well as the above instructions for location of the...

Page 4: ...the sensor are shown in the Technical Specifications chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP swit...

Page 5: ...below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection s...

Page 6: ...ectrical installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommende...

Page 7: ...tenance return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 ha...

Page 8: ...r industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Rep...