EsiWelma Sensigas URS20SI Quick Start Manual Download Page 5

EsiWelma Srl

 

URS20SI_en.doc - rev. 0 

Oxygen detectors – URS20SI 

20/10/2010 

Gas detection systems for industrial environments 

5/8

 

Mechanical installation 
of the optional relay 
card 

The control card can be expanded with a relay card inserted into a dedicated 
connector 

CN3

 with four SPDT relays that will be activated under the following 

conditions: pre-alarm, 1

st

 threshold alarm 2

nd

 threshold alarm and sensor fail, and 

relative LED alerts. 
To install the card, follow the instructions below: 
 
 

Step 1: 

Insert the connection slot provided 
with the relay card into the control 
card, making sure the flexible tab is 
towards the main terminal board. 
Find CN3 connector. 

 

 

 
 
CN3 connector 

 

Connection slot 
(flexible tab) 

 
 
 
 

 

Step 2: 

Fit the relay card snugly 
and pull the flexible tab 
of the connection slot 
towards the main 
terminal board. 
 
 
 
 
 
Flexible tab 
 
 
 

 

 
 

Step 3: 

Check the position of the card. Make sure 
that all the card pins fit into the CN3 
connector and push slightly upwards to 
check that the flexible tab on the connection 
slot keeps the card in place. 
 
 
 
 
 
 

 
Step 4: 

Tick the check box with a 
permanent marker to 
indicate the presence of 
the relay card in the device 
 

 

 

IP65 

TYPE URS20SI

 

 

2,5 W 

Summary of Contents for Sensigas URS20SI

Page 1: ...nd more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SI sensors can be...

Page 2: ...thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up to 200 at 1...

Page 3: ...rs must be located at the breathing height of the occupants in the premises Take into consideration the following specific installation guidelines as well as the above instructions for location of the...

Page 4: ...the sensor are shown in the Technical Specifications chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP swit...

Page 5: ...below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection s...

Page 6: ...ectrical installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommende...

Page 7: ...tenance return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 ha...

Page 8: ...r industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Rep...

Reviews: