EsiWelma Sensigas URS20SI Quick Start Manual Download Page 3

EsiWelma Srl

 

URS20SI_en.doc - rev. 0 

Oxygen detectors – URS20SI 

20/10/2010 

Gas detection systems for industrial environments 

3/8

 

Sensors lifetime 

Sensor average lifetime (see technical characteristics) is referred to a typical usage 
in a pollution-free environment. Presence of a high concentration of pollutants can 
shorten the lifetime of the sensing element. 

Once the detection system starts up, it has to be supplied with energy during all the 
lifetime of its sensors. 

Seasonal use of the detection system is not recommended. 

 

Installation 

 

Oxygen excess 

Since oxygen weighs more or less the same as air, unless there is forced or natural air 
circulation, it tends to spread at the point of the leak. 
So, the excess oxygen detectors must be installed near any likely leakage points, in 
order to detect the excess oxygen as quickly as possible. 

 

Oxygen deficiency 

Detection of oxygen deficiency has the purpose of indirectly detecting the presence of 
other gases that deplete the oxygen in the air, therefore causing asphyxiation problems, 
for example. 
In this case, the detectors must be located at the breathing height of the occupants in the 
premises. 

 

 

Take into consideration the following specific installation guidelines, as well as the above 
instructions, for location of the detectors. 

The detectors must be installed: 

1.  where accidental gas leakages are possible 
2.  at least 1.5m away from heat sources or from vent holes 
3.  not in spaces where ventilation is poor and where gas pockets may form 
4.  away from hindrances to natural gas flow 
5.  away from equipment that may leak gas during normal operations 
6.  in environments with a temperature range of -20°C to 50°C and relative humidity 

below 90% (non-condensing) 

7.  Disconnect equipment from the power supply when mounting and dismantling 

detectors. 

 

Special 
recommendations 

 

CAUTION:  

safety is guaranteed only if cover is screwed on tight. 

Tighten the cover clockwise, and when it is screwed on, make sure that 
there is no more than 0.5 mm between housing and cover. This guarantees 
that it is screwed on tight. Remember to tighten the hexagon locking grub 
screw that fits into the end of the cover. 

It is not essential to comply with the words << DO NOT OPEN WHEN 
ENERGISED >>, since this product is suitable for use in non-hazardous 
areas. In any case, make the area safe before opening the sensor cover. 

 

Summary of Contents for Sensigas URS20SI

Page 1: ...nd more in general where oxygen is stored Oxygen deficiency is an indirect measurement of the presence of other explosive or asphyxiant gases that deplete the oxygen in the air URS20SI sensors can be...

Page 2: ...thresholds 4 20mA Output reference selection 4mA 0 O2 20mA 30 O2 0mA no alarm 10mA 1st threshold alarm 20mA 2nd threshold alarm by jumper selectable polarity 4 20mA output load resistor up to 200 at 1...

Page 3: ...rs must be located at the breathing height of the occupants in the premises Take into consideration the following specific installation guidelines as well as the above instructions for location of the...

Page 4: ...the sensor are shown in the Technical Specifications chapter In order to change the default settings switch off the power supply input the new settings at the JP2 jumper circuit or at the S1 DIP swit...

Page 5: ...below Step 1 Insert the connection slot provided with the relay card into the control card making sure the flexible tab is towards the main terminal board Find CN3 connector CN3 connector Connection s...

Page 6: ...ectrical installation The sensors are factory calibrated so they normally do not require any other calibration once installed Still after installation an operational check of the sensors is recommende...

Page 7: ...tenance return the sensor concerned to the supplier installer who in turn will send it back to the manufacturer Sensors may need to be re calibrated using the TUL40 calibration kit and the TUS40 20 ha...

Page 8: ...r industrial environments 8 8 Installation data To be filled in by Installer Installer s stamp and signature Installation site Product order number Part Number Manufacturing date Installation date Rep...

Reviews: