ESD C.3034.02 Manual Download Page 1

CAN-CBX-THERMO    

Manual • Doc.-No.: C.3034.21 / Rev. 1.2

Page 1 of  123

                                                               esd electronics gmbh
             Vahrenwalder Str. 207 • 30165 Hannover • Germany
                                                                   http://www.esd.eu   
Phone: +49 (0) 511 3 72 98-0 • Fax: +49 (0) 511 3 72 98-68

CAN-CBX-THERMO

4 Thermocouple Interfaces

Manual

to Product C.3034.02

Summary of Contents for C.3034.02

Page 1: ...3034 21 Rev 1 2 Page 1 of 123 esd electronics gmbh Vahrenwalder Str 207 30165 Hannover Germany http www esd eu Phone 49 0 511 3 72 98 0 Fax 49 0 511 3 72 98 68 CAN CBX THERMO 4 Thermocouple Interface...

Page 2: ...this documentation are reserved by esd Distribution to third parties and reproduction of this document in any form whole or in part are subject to esd s written approval 2019 esd electronics gmbh Hann...

Page 3: ...s version 1 0 First English version 1 1 Safety Information revised Typographical Conventions inserted 3 Technical data revised 4 2 4 3 Chapter revised 5 4 Conductor cross section for 24V connector cor...

Page 4: ...nclude a warning relating to property damage DANGER Danger statements indicate a hazardous situation which if not avoided will result in death or serious injury WARNING Warning statements indicate a h...

Page 5: ...Other operating positions are not allowed Never let liquids get inside the CAN CBX module Otherwise electric shocks or short circuits may result Protect the CAN CBX module from dust moisture and steam...

Page 6: ...aintenance by the user The CAN CBX module does not require any manual configuration of the hardware Unauthorized intervention in the device voids warranty claims Disposal Devices which have become def...

Page 7: ...ch Labelling to Name in Schematic Diagram 24 4 4 Installation of the Module Using InRailBus Connector 25 4 4 1 Connecting Power Supply and CAN Signals to CBX InRailBus 26 4 4 2 Connection of the Power...

Page 8: ...and Product specific Values 54 8 9 2 Device Type 1000h 56 8 9 3 Error Register 1001h 57 8 9 4 Pre defined Error Field 1003h 58 8 9 5 COB ID of SYNC Message 1005h 60 8 9 6 Communication Cycle Period 1...

Page 9: ...2 8 11 3 Channel Enabled 2401h 103 8 11 4 Accu N 2402h 104 8 11 5 Average N 2403h 105 8 11 6 Local Temperature at PCB 2420h 106 8 11 7 Local Temperature at the Last Calibration 2421h 107 8 11 8 Calibr...

Page 10: ...t 1 hV can be achieved For cold junction compensation the temperature of the sensor clamp is measured by a digital temperature sensor The conversion of the four thermocouple inputs is realized by four...

Page 11: ...us has to be terminated at both ends esd offers special T connectors and termination connectors Additionally the CAN_GND signal has to be connected to earth at exactly one point in the CAN network For...

Page 12: ...12 of 123 7 Send NMT Start command to module The PDOs are sent on 0180h Module number 0280h Module number 0380h Module number 0480h Module number The Process Value PV is sent in the data bytes 0 3 Th...

Page 13: ...rew connection X500 4 high resolution thermocouple interfaces CAN 5 pin line connector with spring cage connection X400 CAN interface Only for test and programming purposes X200 6 pin connector the co...

Page 14: ...in line connector with spring cage connection or via InRailBus connector CAN CBX TBUS CAN Controller MB90F497 ISO11898 1 CAN 2 0 Electrical isolation of CAN interfaces against other units Isolation vo...

Page 15: ...dependent 0 1pC Input impedance 1 Mq Conversion rate 2 5 Hz 1000 Hz Resolution 1 rV at 25 Hz conversion rate s 0 1pC Maximum sensor voltage 1 024 V Electrical isolation electrical isolation of thermoc...

Page 16: ...Diagram Fig 2 Connections of the CAN CBX THERMO module NOTICE Read chapter Quick Start on page 11 before you start with the installation of the hardware INFORMATION Refer to page 34 for information o...

Page 17: ...e Fig 4 to minimize the error of the cold junction compensation for order information see page 122 NOTICE Generally a standard thermocouple length 3 m comes only with two signal lines If a shielded th...

Page 18: ...Hardware Installation Manual Doc No C 3034 21 Rev 1 2 CAN CBX THERMO Page 18 of 123 Fig 4 Connection with cable housing to improve cold junction compensation...

Page 19: ...described in the following chapters 4 2 1 Indicator States In principle there are 8 indicator states distinguished Indicator state Display on LED constantly on off LED constantly off blinking LED blin...

Page 20: ...Error red off no error 1 flash CAN controller is in Error Active state on CAN controller state is Bus Off or coding switch position ID node 7Fh when switching on see Special Indicator States on page 2...

Page 21: ...ult values are loaded internal watchdog has triggered indicator state is continued until the module resets or an error occurs at the outputs blinking Sensor error emergency error code 5030h e g sensor...

Page 22: ...cription CANopen Status LED 3 flashes and CAN Error LED on Invalid nodeID The coding switches for the Node ID are set to an invalid ID value when switching on The firmware application will be stopped...

Page 23: ...a reset e g NMT reset the settings are read again 4 3 1 Setting the Node ID via Coding Switch The address range of the CAN CBX module can be set decimal from1 to 127 or hexadecimal from 01h to 7Fh The...

Page 24: ...he baud rate can be taken from the following table Setting Bit rate Kbit s 0 1000 1 666 6 2 500 3 333 3 4 250 5 166 6 125 7 100 8 66 6 9 50 Ah 33 3 Bh 20 Ch 12 5 Dh 10 Eh 800 Fh 83 3 Table 11 Index of...

Page 25: ...ap it onto the mounting rail using slight pressure Plug the bus connectors together to contact the communication and power signals in parallel with one The bus connectors can be plugged together befor...

Page 26: ...9 Mounted CAN CBX module 4 4 1 Connecting Power Supply and CAN Signals to CBX InRailBus To connect the power supply and the CAN signals via the InRailBus a terminal plug is needed The terminalplug is...

Page 27: ...ected and must not be supplied by two independent power sources at the same time Fig 11 Connecting the power supply voltage to the CAN CBX station Earthing of the Mounting Rail NOTICE The module is co...

Page 28: ...nds of the CAN CBX station must not be connected to the CAN bus because this would cause incorrect branching A bus termination must be connected to the CAN connector of the CAN CBX module at the end o...

Page 29: ...act order no 19 21 90 0 included in the scope of delivery For conductor connection and conductor cross section see page 34 Pin Position Pin Assignment Labelling on Housing 24V M P Labelling on connect...

Page 30: ...layer is designed according to ISO 11898 2 The CAN bus signals are electrically isolated from the other signals via a digital isolator and a DC DC converter Fig 13 CAN Interface The CAN interface can...

Page 31: ...Pin Position Pin Assignment device connector with labelling Labelling Signal Pin G CAN_GND 1 L CAN_L 2 Sh Shield 3 H CAN_H 4 5 Signal description CAN_L CAN_H CAN signals CAN_GND reference potential o...

Page 32: ...r CAN CBX TBUS Phoenix Contact ME 22 5 TBUS 1 5 5 ST 3 81 KMGY Pin Position Pin Assignment Pin Signal 5 M24 GND 4 P24 24 V 3 CAN_GND 2 CAN_L 1 CAN_H S FE PE_GND Signal Description CAN_L CAN_H CAN sign...

Page 33: ...ection and conductor cross section see page 34 Pin Position Pin Assignment Signal Pin Description S4 1 Interface thermocouple 4 Shield 2 S4 3 S3 4 Interface thermocouple 3 Shield 5 S3 6 S2 7 Interface...

Page 34: ...errule without plastic sleeve max 2 5 mm 1 5 mm 1 5 mm Conductor cross section stranded with ferrule with plastic sleeve min 0 25 mm 0 25 mm 0 25 mm Conductor cross section stranded with ferrule with...

Page 35: ...for CAN network design margin must be given for signal loss across the complete system and cabling parasitic loadings network imbalances ground offsets against earth potential and signal integrity The...

Page 36: ...an adequate conductor cross section J 0 22 mm has to be used The voltage drop over the wire has to be considered 2 For light industrial environment use at least a two wire CAN cable Connect K the two...

Page 37: ...If a mixed application of single twisted and double twisted cables is unavoidable take care that the CAN_GND line is not interrupted L Deviations from the bus structure can be realized by the usage of...

Page 38: ...he wire has to be considered 2 For heavy industrial environment use a four wire CAN cable Connect two twisted wires to the data signals CAN_H CAN_L and the other two twisted wires to the reference pot...

Page 39: ...nector For further information on this read the CAN T Connector Manual order no C 1311 21 Alternatively a T connector can be used in which the shield potential is looped through e g the DSUB9 connecto...

Page 40: ...ons of the CiA like standard values of the cross section depending on the cable length are described in the CiA recommendation CiA 303 1 see CiA 303 CANopen Recommendation Part 1 Cabling and connector...

Page 41: ...nCab GmbH u erer Eichwald 74535 Mainhardt Germany www concab de e g BUS PVC C 1x 2x 0 22 mm Part No 93 022 016 UL appr BUS Schleppflex PUR C 1x 2x 0 25 mm Part No 94 025 016 UL appr 6 6 2 Cable for He...

Page 42: ...ne and load impedance are equal these reflections are avoided This test measures the series resistance of the CAN data pair conductors and the attached terminating resistors To test it please 1 Turn o...

Page 43: ...of the CAN_GND wires 7 3 Short Circuit in CAN Wiring A CAN bus might possibly still be able to transmit data if there is a short circuit between CAN_GND and CAN_L but generally the error rate will in...

Page 44: ...through the CAN circuits please use a resistance measuring device and 1 Switch off the node and disconnect it from the network see figure below 2 Measure the DC resistance between CAN_H and CAN_GND se...

Page 45: ...unication Object Emergency Id Emergency Data Object NMT Network Management Master SDO Service Data Object Sync Sync frame Telegram PDOs Process Data Objects PDOs are used to transmit process data In t...

Page 46: ...t directory is basically a sorted group of objects which can be accessed via the CAN network Each object in this directory is addressed with a 16 bit index The index in the object directories is repre...

Page 47: ...vice Access via this channel is possible in operational and pre operational status The SDOs Service Data Objects are transmitted on ID 600h Node ID request The server acknowledges the parameters on ID...

Page 48: ...s on the syntax and further command codes can be found in 1 Command Number of data bytes Command code Write Request Initiate Domain Download 1 2 3 4 2Fh 2Bh 27h 23h Write Response Initiate Domain Down...

Page 49: ...pped to PDO 06060000h access failed due to an hardware error 06070010h wrong number of data bytes 06070012h service parameter too long 06070013h service parameter too small 06090011h wrong sub index 0...

Page 50: ...t 1802h TPDO4 480h Node ID PDO4 from CAN CBX THERMO object 1803h Client SDO 580h Node ID SDO from CAN CBX THERMO Server SDO 600h Node ID SDO to CAN CBX THERMO Node Guarding 700h Node ID configurable v...

Page 51: ...ess value 2 9130h 2 TPDO3 380h Node ID 4 byte Process value 3 9130h 3 TPDO4 480h Node ID 4 byte Process value 4 9130h 4 Per default only the Process_Values 1 to 4 object 9130h sub index 1 4 are mapped...

Page 52: ...ission type 0 and data has changed s cyclic synchronous The transmission is initiated if a defined number of SYNC messages have been received PDO transmission type 1 240 s event controlled asynchronou...

Page 53: ...the local EEPROM if the command save is called see page 66 Data type data type e g unsigned 8 unsigned 32 Access mode allowed access modes to this parameter ro read_only This parameter can only be re...

Page 54: ...e string ro default CAN CBX THERMO 1009h Manufacturer Hardware Version visible string ro default depending on version 100Ah Manufacturer Software Version visible string ro default depending on version...

Page 55: ...mPar 20h rw 1803h 5 4 Transmit PDO Parameter PDO CommPar 20h rw 1A00h 2 1 Transmit PDO Mapping PDO Mappping 21h rw 1A01h 2 2 Transmit PDO Mapping PDO Mappping 21h rw 1A02h 2 3 Transmit PDO Mapping PDO...

Page 56: ...5 6 7 8 603h 0h 8h 40h 00h 10h 00h 00h 00h 00h 00h Read Request Index 1000h Sub Index The CAN CBX module no 3 responds to the client by means of read response with identifier 583h 580h Node ID with th...

Page 57: ...Access type ro Default value 0 The following bits of the error register are being supported at present Bit Meaning 0 generic 1 current 2 voltage 3 temperature 4 communication error overrun error stat...

Page 58: ...full the oldest entry is deleted for the latest entry This module supports a maximum of 10 error entries When the 11th error occurs the oldest error entry is deleted In order to delete the entire err...

Page 59: ...d error heartbeat error 8140h Recovered from Bus Off 8240h Unexpected SYNC data length 6000h Software error EEPROM checksum error no transmission of this error message as emergency message 6110h Inter...

Page 60: ...e unsigned 32 Access mode rw Default value see chapter 8 9 1 page 54 Structure of the parameter Bit No Value Meaning 31 MSB do not care 30 0 1 0 Device does not generate SYNC message 1 Device generate...

Page 61: ...2 Page 61 of 123 8 9 6 Communication Cycle Period 1006h INDEX 1006h Name Communication Cycle Period Data type unsigned 32 Access mode rw Default value 0 us Value range of the parameter Value Meaning 0...

Page 62: ...21 Rev 1 2 CAN CBX THERMO Page 62 of 123 8 9 7 Manufacturer Device Name 1008h INDEX 1008h Name manufacturer device name Data type visible string Default value see chapter 8 9 1 page 54 For detailed d...

Page 63: ...ad similarly to reading the manufacturer s device name via the domain upload protocol Please refer to 1 for a detailed description of the upload 8 9 9 Manufacturer Software Version 100Ah INDEX 100Ah N...

Page 64: ...l be used preferentially Use the node guarding only for existing systems and not for new developments Guard time and life time factors are evaluated together Multiplying both values will give you the...

Page 65: ...bit identifiers INDEX 100Eh Name node guarding identifier Data type unsigned 32 Access mode rw Default value 700h Node ID Structure of the parameter node guarding identifier Bit No Meaning 31 MSB 30 r...

Page 66: ...dex Sub index Description Value range Data type Access mode 1010h 0 number_of_entries 4 unsigned 8 ro 1 save_all_parameters objects 1000h 9FFFh no default write 65 76 61 73h ASCII e v a s unsigned 32...

Page 67: ...index 1 4 On read access to the appropriate sub index the CAN CBX module provides information about its storage functionality with the format described in the following Bit 31 2 1 0 Inhalt reserved au...

Page 68: ...lue range Data type Access mode 1011h 0 number_of_entries 4 unsigned 8 ro 1 restore_all_default_parameters objects 1000h 9FFFh no default write 64 61 6F 6Ch ASCII d a o l unsigned 32 rw 2 restore_comm...

Page 69: ...e load 64h 61h 6Fh 6Ch sequence in CAN telegram in object 1011h sub index 1 4 Onread access to the appropriate sub index the CANopen device provides information about its default parameter restoring c...

Page 70: ...lue 80h Node ID This object defines the COB ID of the emergency object EMCY The structure of this object is shown in the following table Bit No Value Meaning 31 MSB 0 1 0 EMCY exists is valid 1 EMCY d...

Page 71: ...Page 71 of 123 8 9 15 Inhibit Time EMCY 1015h INDEX 1015h Name inhibit_time_emergency Data type unsigned 16 Access mode rw Value range 0 FFFFh Default value 0 The Inhibit Time for the EMCY message can...

Page 72: ...nsmits a heartbeat message on the CAN bus on the node guarding identifier see object 100Eh One or more heartbeat consumers receive the message It has to be received within the heartbeat time stored on...

Page 73: ...ed 16 Node ID Node Id of the heartbeat producer to be monitored heartbeat_time Within this time ms the heartbeat producer has to transmit the heartbeat on the node guarding ID to avoid the transmissio...

Page 74: ...e is higher than 0 it is active and stops the node life guarding see page 64 If the value of the producer heartbeat time is set to 0 transmitting heartbeats by this module is stopped Index Sub index D...

Page 75: ...ed 32 ro 4 serial_number 0 FFFFFFFFh unsigned 32 ro Description of the variables vendor_id This variable contains the esd vendor ID This is always 0000 0017h product_code Here the esd article number o...

Page 76: ...first two characters of the serial number are letters which designate the manufacturing lot The following characters represent the actual serial number In the two MSB of serial_no the letters of the...

Page 77: ...bject defines whether a counter is mapped into the SYNC message or not and further the highest value the counter can reach The value range of the object is described in the following table Value Descr...

Page 78: ...he expected configuration or not The content of the parameters is not evaluated by the firmware Index Sub index Description Value range Default Data type Access mode 1020h 0 no_of_entries 2 2 unsigned...

Page 79: ...communication_error or output_error Index Sub index Description Value range Default Data type Access mode 1029h 0 no_of_error_classes 1 1 unsigned 8 ro 1 communication_error 0 2 0 unsigned 8 rw Meani...

Page 80: ...mented to be able to start CANopen nodes in environments without NMT master Via NMT startup the auto startup of a CANopen node can be switched on or off Further features of the parameters NMT startup...

Page 81: ...ameters Data type unsigned 16 Index Sub index Description Value range Default Data type Access mode 1F91h 0 number_of_entries 1 1 unsigned 8 ro 1 NMT master detection timeout 0 FFFFh 64h unsigned 16 r...

Page 82: ...by PDO 1 C00007FFh 40000280h Node ID unsigned 32 rw 2 transmission type 0 FFh FFh unsigned 8 rw 3 inhibit time 0 FFFFh 0 unsigned 16 rw 4 reserved 0 FFh 0 unsigned 8 const 5 event timer 0 FFFFh 0 uns...

Page 83: ...FFFFFFFFh 9100 0120h unsigned 32 rw 1A01h 0 number of entries 2 1 unsigned 8 rw 1 Process_Value_2 0 FFFFFFFFh 9130 0220h unsigned 32 rw 2 Field_Value_2 0 FFFFFFFFh 9100 0220h unsigned 32 rw 1A02h 0 n...

Page 84: ...ned 32 6131h AI_physical_unit_PV unsigned 32 6132h AI_decimal_digits_PV unsigned 8 6150h AI_status unsigned 8 9100h AI_FV integer 32 9103h AI_interrupt_delta_input_FV integer 32 9130h AI_PV integer 32...

Page 85: ...3034 21 Rev 1 2 Page 85 of 123 wxyz w w w y y w w w w w y y w y y w w wxyz w wy w w w w w wxyz w w y w y w w w y y w w w w wy w w w y 8 10 2 Relationship Between the Implemented Analog Input Objects F...

Page 86: ...x 1 4 The parameter contains the type of the connected thermocouple The end number of the variable name is the number of the thermocouple interface see also 4 Value range Value of the parameter Descri...

Page 87: ...unsigned 32 wo Function Writing the ASCII strings cali leads to the automatic calibration of the corresponding channel The automatic calibration starts automatically after detection of new thermocoupl...

Page 88: ...1 unsigned 8 rw 2 AI_operating_mode_2 0 1 1 unsigned 8 rw 3 AI_operating_mode_3 0 1 1 unsigned 8 rw 4 AI_operating_mode_4 0 1 1 unsigned 8 rw Description of parameter AI_operating_mode_x x 1 4 The pa...

Page 89: ...sampling rates of the single channels can be set each independent from the others The resolution is 1 s The following values are supported Value range Allowed parameter values 2 Sample time Sampling...

Page 90: ...D 0000h FA26 0000h unitSensorType_4 unsigned 32 ro The default values unitSensorType_x x 1 4 depend on the sensor type set With the default setting of object 6110h 28h 40 voltage measurement it would...

Page 91: ...or physical units Prefix Factor Notation index 100 00h micro 10 6 FAh SI Numerator and SI Denominator contain the physical units Coding of the physical units International symbol Name of unit Notation...

Page 92: ...s_PV_2 0 3 3 unsigned 8 rw 3 AI_decimal_digits_PV_3 0 3 3 unsigned 8 rw 4 AI_decimal_digits_PV_4 0 3 3 unsigned 8 rw Description of the parameter AI_decimal_digits_PV_x x 1 4 This parameter contains t...

Page 93: ...state of the corresponding analog input channel Bit 7 6 5 4 3 2 1 0 Meaning reserved 3 not supported 3 reserved 3 Negative Overload Positive Overload Not Valid 3 These bits are always returned as 0 Va...

Page 94: ...r limit is exceeded The bits 1 and 2 cannot be set at the same time If no sensor is connected only bit Not Valid is set If the temperature exceeds the range bits Not Valid AND the corresponding Overlo...

Page 95: ...cess 9100h 0 Number_of_entries 4 4 unsigned 8 ro 1 AI_FV_1 80000000h 7FFFFFFFh integer 32 ro 2 AI_FV_2 80000000h 7FFFFFFFh integer 32 ro 3 AI_FV_3 80000000h 7FFFFFFFh integer 32 ro 4 AI_FV_4 80000000h...

Page 96: ...delta_input_FV_4 80000000h 7FFFFFFFh 0 integer 32 rw Description of the parameter AI_interrupt_delta_input_FV_x x 1 4 If a field value is mapped on a PDO and the deviation of the field value is higher...

Page 97: ...000000h 7FFFFFFFh integer 32 ro 2 AI_PV_2 80000000h 7FFFFFFFh integer 32 ro 3 AI_PV_3 80000000h 7FFFFFFFh integer 32 ro 4 AI_PV_4 80000000h 7FFFFFFFh integer 32 ro Description of the variable AI_PV_x...

Page 98: ...f the parameter AI_interrupt_delta_input_PV_x x 1 4 If a process variable is mapped on a PDO and the deviation of the process variable is higher than specified in AI_interrupt_delta_input_PV_x this PD...

Page 99: ...nteger 32 rw 3 AI_interrupt_lower_limit_PV_3 80000000h 7FFFFFFFh 80000000h integer 32 rw 4 AI_interrupt_lower_limit_PV_4 80000000h 7FFFFFFFh 80000000h integer 32 rw Description of the parameter AI_int...

Page 100: ...nteger 32 rw 3 AI_interrupt_upper_limit_PV_3 80000000h 7FFFFFFFh 7FFFFFFFh integer 32 rw 4 AI_interrupt_upper_limit_PV_4 80000000h 7FFFFFFFh 7FFFFFFFh integer 32 rw Description of the parameter AI_int...

Page 101: ...ature PCB integer 16 2422h Delta_calibration_temperature PCB integer 16 2423h Estimated_junction_temperature 4 integer 16 2503h Gain_correction integer 16 2504h Gain_correction_PGA 2 integer 16 2505h...

Page 102: ...rw Description of the parameter ADC_PGA_x x 1 4 This parameter sets the gain PGA of the A D converters ADS1255 Value range The gain Vx is Vx 2 ADC_PGA_x The gain 2 4 8 and 16 can be set The gain is tr...

Page 103: ...o 4 channel_enabled_4 0 1 boolean ro Description of the variable channel_enabled_x x 1 4 If a sensor has been detected for the measuring channel this variable returns the actual value of the object AI...

Page 104: ...meter accu_count_x x 1 4 This parameter defines the number ofanalog values to be added The parameter accu_count reduces the data rate while improving the resolution The number of accumulations is n Nu...

Page 105: ...arameter average_count_x x 1 4 This parameter defines how many analog values are used to calculate the moving average After every conversion a new average is available because the A D values are buffe...

Page 106: ...umber_of_entries 4 4 unsigned 8 ro 1 local_temperature 8000h 7FFFh integer 16 ro Description of the variable local_temperature This variable contains the value of the temperature on the circuit board...

Page 107: ...mp_last_cal_2 integer 16 ro 3 last_calibration_temp_3 8000h 7FFFh temp_last_cal_3 integer 16 ro 4 last_calibration_temp_4 8000h 7FFFh temp_last_cal_4 integer 16 ro The default value temp_last_cal_x x...

Page 108: ...6 rw 4 delta_calibration_temp_4 0 FFFFh 0 unsigned 16 rw Description of the variable delta_calibration_temp_x The ADS1255 performs a self calibration if the temperature of the PCB 2420h deviates more...

Page 109: ...ble estimated_junction_temp_x This variable contains the estimated values of the channel dependent junction temperature on the circuit board in steps of 1 256 C The value is coded as described in the...

Page 110: ...the calibration data adjusted by esd are reactivated 8 11 10 1 Calibration and Process Field Value Calculation In the following formulas the parameter names are shown without the channel identifier at...

Page 111: ...al correction factor corr gc PGA gc PGAy _ _ 1 with gc_PGA1 Object 2503h gain correction factor PGA 1 gc_PGAy Objects 2504h 2505h 2506h additional gain correction for the gain y 2 3 4 PGA 2 2504h PGA...

Page 112: ...2 CAN CBX THERMO Page 112 of 123 3 Temperature Calculation and CJC PV Tab PV T U with PVT Object 9130h process value mapped to PDOs PVT f SensorType obj 6110h PVU EJT object 2423h Tab application of t...

Page 113: ...can be disabled Only if this parameter is disabled the estimated junction temperature can be set manually 1 If the value is set to 1 the variable estimated_junction_temp_X index 2423h sub index 1 4 i...

Page 114: ...0h 7FFFh 6 integer 16 rw 2505h 0 Number_of_entries 4 4 unsigned 8 ro 1 gain_correction_PGA 3_1 8000h 7FFFh 6 integer 16 rw 2 gain_correction_PGA 3_2 8000h 7FFFh 6 integer 16 rw 3 gain_correction_PGA 3...

Page 115: ...p_offset_3 8000h 7FFFh 0 integer 16 rw 4 channel_temp_offset_4 8000h 7FFFh 0 integer 16 rw Description of the variable channel_temp_offset_x x 1 4 The variable channel_temp_offset_x contains the tempe...

Page 116: ...FFFh 0 integer 16 rw 2 u_offset_2 8000h 7FFFh 0 integer 16 rw 3 u_offset_3 8000h 7FFFh 0 integer 16 rw 4 u_offset_4 8000h 7FFFh 0 integer 16 rw Description of the parameter u_offset_x x 1 4 By means o...

Page 117: ...8 ro 5 This object is not supported yet Description of the parameter slope_compensation_mode With the slope_compensation_mode a junction temperature slope compensation can be enabled or disabled for a...

Page 118: ...s of the firmware The module then can not be operated further INFORMATION esd offers the program CANfirmdown for a firmware update Please contact our support for this In normal CiA 301 mode the object...

Page 119: ...tion about object 1F51h and the firmware update please refer to 2 8 12 2 Verify Application Software 1F52h Index Sub index Description Value range Default Data type Access mode 1F52h 0 Number of entri...

Page 120: ...G Blomberg Technical data is taken from the Phoenix Contact website https www phoenixcontact com online portal de PCB plug connector FKCT 2 5 4 ST KMGY 1921900 downloaded 2014 10 29 7 Phoenix Contact...

Page 121: ...CAN CBX THERMO Manual Doc No C 3034 21 Rev 1 2 Page 121 of 123 11 Declaration of Conformity...

Page 122: ...1 KMGY 2713722 C 3000 01 CAN CBX TBUS Connector Terminal plug of the CBX InRailBus for the connection of the 24 V power supply voltage and the CAN interface Female type Phoenix Contact order informati...

Page 123: ...table Please download the manuals as PDF documents from our esd website www esd eu for free Manuals Order No CAN CBX THERMO ME Manual in English C 3034 21 Table 14 Available manuals Printed Manuals If...

Reviews: