EpiSensor ZDR-16 Install Sheet Download Page 1

Install Sheet

ZDR-16 

// 

Wireless Demand Response Controller

Document Ref. EPI-065-02

Installation & Safety Notes

NEVER work alone.

Use appropriate personal protective equipment (PPE) and follow safe electrical work practices.

Only qualified electrical workers should install this equipment. Such work should be performed only after 
reading the entire set of installation instructions.

If the equipment is not used in a manner specified by EpiSensor, the protection provided by the equipment 
may be impaired.

Before performing visual inspections, tests, or maintenance on this equipment, disconnect all sources of 
electric power. Assume that all circuits are live until they have been completely de-energized, tested, and 
tagged. Pay particular attention to the design of the power system. Consider all sources of power, including 
the possibility of backfeeding.

Turn off all power supplying the meter and the equipment in which it is installed before working on it.

Always use a properly rated voltage sensing device to confirm that all power is off.

Before closing all covers and doors, inspect the work area for tools and objects that may have been left 
inside the equipment or panel.

When removing or installing metering or other equipment, do not allow it to extend into the energised bus.

The successful operation of this equipment depends upon proper handling,

Neglecting fundamental installation requirements may lead to personal injury as well as damage to 
electrical equipment or other property.

Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the energy meter is 
installed, disconnect all input and output wires to the energy meter.

High voltage testing may damage electronic components contained in the meter.

Failure to follow these instructions will result in death or serious injury.

HAZARD OF ELECTRIC SHOCK, 

EXPLOSION, OR ARC FLASH

EpiSensor equipment should be installed, operated, serviced and maintained only by qualified personnel. 
EpiSensor does not assume any responsibility for any consequences arising out of the use of this 
equipment. 

The ZDR-16 voltage measurement inputs are rated for up to 277 V L-N or 480 V L-L. For any voltage 
exceeding 277 V L-N, an auxiliary power source must be used. Consult the ZDR-16 datasheet for more 
information on available product variants. For voltages exceeding 480 V L-L, a voltage transformer must 
be used. 

Fuse for neutral terminal is required if the source neutral connection is not grounded.

Clearly label the device’s disconnect circuit mechanism and install it within easy reach of the operator.

The fuses / circuit breakers must be rated for the installation voltage and sized for the available fault 
current.

Depending on the type of current transformers used with the EpiSensor ZDR, shorting links may be 
required. Please consult the user guide for more information.

If Voltage Transformers are used, the VT ratio setting should be adjusted on the ZDR settings page on the 
Gateway.

By default, there will not be a cable included for mains reference voltages

ZDR’s using Rogowski coil or milliamp Current Transformers are individually calibrated and the current 
transformer cables should not be extended or interchanged.

CT1

Voltage References & Current Transformer Wiring Diagram

Important: 

Fused disconnect 

or circuit breakers (not 
supplied) to protect 0.75mm

2

 

conductor according to local 
electrical regulations (min. 
500mA)

CT3

CT2

Phase C

Phase A

Neutral

Phase B

L1

L2

L3

N

Configuration: 4 WIRE WYE

ANSI Meter Form: 9S/16S

Inputs: 3 x Vref, 3 x CT

Note: configure ZDR on Gateway for 9S/16S

3-Phase 
Supply

L1

L2

L3

N

CT1

-

  +

CT2

-

  +

CT3

-

  +

Note: 

Insulation 

colours for CT / 
Rogowski coil cables 
can vary

Note: 

By default, a 

single phase supply is 
taken from L1 and N to 
power ZDR (not shown 
on this diagram). This 
can be replaced with a 
separate auxiliary 
supply if required.

Reviews: