1
THE HEAT PUMP AC – WITH NO OUTDOOR UNIT
®
INSTALLATION MANUAL
Page 1: ...1 THE HEAT PUMP AC WITH NO OUTDOOR UNIT INSTALLATION MANUAL...
Page 2: ...than when the unit is in operation It is your responsibility to install the system safely and to know it well enough to be able to instruct a customer in its safe use The precautions listed in this In...
Page 3: ...he unit to leak The unit is equipped with an anti tip sensor If the sensor shows the unit was tipped the warranty is void When certifying the unit a factory technician will check this sensor and if it...
Page 4: ...on Condensate Removal P Heat Pump Only E Heat Pump 1K Electric Resistance Heat K Heat Pump 2K Electric Resistance Heat F Heat Pump with Integrated FCU 8 3 100 8 100 BTu h 9 3 139 10 500 BTu h 1 115v 6...
Page 5: ...l bracket is securely hung at least 2 screws are in cement or wood other 4 screws are TOGGLER brand SNAPTOGGLE Heavy Duty Toggle Bolts model number BB or BBS in 1 4 Compressor is unlocked Approved ext...
Page 6: ...t modify the safety or adjustment devices without written authorization from Ephoca Repairs or maintenance must be performed by qualified personnel in accordance with this manual Do not modify or tamp...
Page 7: ...result in damage to the unit damage to property personal injury or death WARNING FALLING OBJECT HAZARD Failure to mount the unit securely can result in property damage injury or death WARNING ELECTRIC...
Page 8: ...8...
Page 9: ...y properly outside to ensure that no water will penetrate Seal the sleeve tightly to the wallboard inside the room If not completely sealed the powerful fan can suck insulation from inside the wall in...
Page 10: ...ded in the packaging and are required for installation If a part is missing please contact Customer Service 1 Bracket for wall mounting 2 Template for holes 3 Wall mount touch controller For models wi...
Page 11: ...ay 3 Front cover panel 4 Outdoor air suction 5 Outdoor air outlet 6 Internal air intake grille 7 Ventilation filter 8 Condensate drain pipe 9 Temperature sensor 10 Power supply terminal block 11 Side...
Page 12: ...ner When used exclusively to heat avoid high wall installation in rooms where the ceiling is greater than 10 feet high Make sure 1 8 of the of the pipe sleeve extends into the room so that the unit wi...
Page 13: ...ssing the unit The HPAC should not touch the wall on either side as it will vibrate slightly during operations and that will create noise even 1 2 will suffice However we highly recommend 2 5 on the s...
Page 14: ...the unit perpendicular to an exterior wall using our optional side wall kit This kit which gets installed inside the wall includes additional fans which assist the air through the additional bend The...
Page 15: ...versions with auxiliary electric heat resistance in order to prevent internal overheating do not disconnect voltage from the unit abruptly Use the CP contact that places the unit in standby mode guara...
Page 16: ...other fastener STEP 4 If using an external drain for condensate drill a hole as indicated on the template for the condensate to drain outside Make sure to drill the hole at a 3 degree downward angle S...
Page 17: ...al connection area C Holes for air vent pipes D Holes for external condensate drain E Anti lifting bracket hole E C A D B 64 15 32 64 2 4 7 64 11 32 7 4 5 32 2 8 4 64 4 16 2 64 1 64 39 16 21 32 1 32 3...
Page 18: ...lection pan to eliminate icing up of the liquid where a solenoid valve controls the flow of the condensate from the internal collection tray to the drain pipe once the maximum level has been reached S...
Page 19: ...necessary to add a siphon before placing the pipe into the sewer drain This siphon must be placed at least 12 under the drain pipe NOTICE When connecting the condensate drain be careful not to squeez...
Page 20: ...the position of the air louver so that air blows downwards instead of upwards STEP 1 Disconnect the power STEP 2 Remove the upper grill STEP 3 Remove the front cover panel by unscrewing the two screw...
Page 21: ...EP 10 Connect the power and turn unit on STEP 11 Press the and keep pressed 10 seconds STEP 12 The dn lower wall symbol flashes on the display STEP 13 Press the key again STEP 14 The up upper wall sym...
Page 22: ...pleted STEP 3 Connect the condensate drain pipe according to the method selected STEP 4 Fasten a screw into the anti lifting hole Anti lifting bracket WARNING EXCESSIVE WEIGHT HAZARD Use two people wh...
Page 23: ...before starting up the compressor Under the unit on the right side by the red label there are two wing nuts that must be completely unscrewed and removed to free the compressor This must be done befor...
Page 24: ...m wattage of the conditioner minimum cable section equal to 1 5 mm2 Power is only supplied using a suitable socket through the supplied plug The power supply is provided with suitable protections agai...
Page 25: ...ING ELECTRICAL SHOCK HAZARD Turn off all electrical power before making any connections All electrical connections and wiring MUST be installed by a qualified electrician and conform to the National C...