Step2:
Mark the installation position with the mounting plate 1. The distance between
the two mounting holes is 300mm.
Step3:
Rotate the direction of mounting plate 1 and mounting plate 2, and install them
again.
2.4 Install the inverter/charger
The inverter/charger can be fixed to the concrete and solid brick walls and
cannot be fixed to the hollow brick wall.
The inverter/charger requires at least 20cm of clearance right and left and
50cm of clearance above and below.
Risk of explosion! Never install the inverter/charger in a sealed enclose with
flooded batteries! Do not install the inverter/charger in a confined area where
the battery gas can accumulate.
Step1:
Determine the installation location and heat-dissipation space. The
inverter/charger requires at least 20cm of clearance right and left and 50cm