CAUTION:
Equipment damage!
Over-charging and excessive gas precipitation may damage the battery
plates and activate material shedding on them. Too high an equalizing
charge or for too long may cause damage.
Please carefully review the specific requirements of the battery used in the system.
Some types of batteries benefit from equalizing charge on a regular basis, which is
able to stir electrolyte, balance battery voltage and accomplish chemical reaction.
Equalizing charge increases battery voltage, higher than the standard complement
voltage, which gasifies the battery electrolyte.
The controller will equalize the battery on 28th each month. The constant equalization
period is 0~180 minutes. If the equalization isn‟t accomplished in one-time, the
equalization recharge time will be accumulated until the set time is finished. Equalize
charge and boost charge are not carried out constantly in a full charge process to
avoid too much gas precipitation or overheating of battery.
NOTE:
1) Due to the influence of ambient circumstance or load working, the battery
voltage can’t be steady in constant voltage, controller will accumulate and
calculate the time of constant voltage working. When the accumulated time
reach to 3 hours, the charging mode will turn to Float Charging.
2) If the controller time is not adjusted, the controller will equalize charge
battery once every month following the inner time.
C) Float Charging
After the Constant voltage stage, the controller will reduce charging current to Float
Voltage setpoint. This stage will have no more chemical reactions and all the charge
current transforms into heat and gas at this time. Then the controller reduces the
voltage to the floating stage, charging with a smaller voltage and current. It will reduce
the temperature of the battery and prevent the gassing and charging the battery
slightly at the same time. The purpose of Float stage is to offset the power
consumption caused by self consumption and small loads in the whole system, while
maintaining full battery storage capacity.
In Float charging stage, loads are able to obtain almost all power from solar panel. If
loads exceed the power, the controller will no longer be able to maintain battery
voltage in Float charging stage. If the battery voltage remains below the Recharge
Voltage, the system will leave Float charging stage and return to Bulk charging stage.
Summary of Contents for Tracer1206AN
Page 2: ......
Page 26: ...22...
Page 38: ...34 Annex II Dimensions Tracer1206 1210AN Unit mm...
Page 39: ...35 Tracer2206AN 2210AN Unit mm...
Page 40: ...36 Tracer3210AN Unit mm...
Page 41: ...37 Tracer4210AN Unit mm Any changes without prior notice Version number 1 0...
Page 42: ......
Page 43: ......