EOS Zeus HD / Zeus L HD - Installation and Operating Instructions
EN-17
Installation
3.1.2 Air inlets and outlets
Air inlets and outlets must be installed in the cabin to ensure sufficient air
flow in the cabin and to prevent the heating element or the heater's electri-
cal lines from becoming damaged.
The required size of the air inlets and outlets depends on the heater out-
put; see 2.4 Technical data,
WARNING
Fire hazard from overheating
The heater can overheat if the air supply is insufficient. There is a
risk of death due to fire.
Ensure that the air inlets and outlets provide sufficient ventila-
tion. Install a fan if necessary.
Commission the cabin only after all air inlets and outlets have
been opened.
If the heating process takes a long time, the underlying reason is that the
heater receives insufficient air. A minimum of 5 times the cabin volume of
air per hour must be exchanged.
If, despite compliance with dimensions, there is still not enough fresh air to
reach the heater, a fan must be installed at the opening outside of the
cabin.
Depending on the location of the heater, the air inlet must be installed
behind or below the heater.
Air outlet
The air outlet must meet the following criteria:
Location: Across from the heater
Height: 30–50 cm above the cabin floor
For more specifications, see 2.4 Technical data,