ET3-12 URINAL FLUSH VALVE - TROUBLESHOOTING YOUR INSTALLATION

 

 

Initial Checks: 

 

 

C

HECK WATER SUPPLY

;  

 

U

NPLUG ALL CABLES

,

 LEAVE UNPLUGGED FOR 

5

 MINUTES

 (

THIS GIVES THE ELECTRONICS A CHANCE 

TO RESET

BEFORE RECONNECTING EVERYTHING CAREFULLY AND CORRECTLY 

 IF MAINS POWERED

:

 

RECONNECT BATTERY BOX TO TRANSFORMER BEFORE SENSOR CABLE 

(

SEE DIAGRAM BELOW

).

 

W

ARNING

 ELECTRONICS WILL BE DAMAGED IF CONNECTED INCORRECTLY

*

 

E

NSURE SCREWED COLLAR CONNECTIONS ARE TIGHT 

(

DO NOT OVERTIGHTEN

); 

 

C

HECK SENSOR WINDOW IS CLEAN AND UNOBSTRUCTED

;  

 

I

F URINAL HAS BEEN OPERATING CORRECTLY FOR SOME TIME

 AND HAS SUDDENLY STOPPED OR 

WATER IS CONSTANTLY RUNNING ON 

 LIKELY CAUSE IS NO POWER

.

 TO CONFIRM 

-

 CHANGE 

BATTERIES

,

 UNIT SHOULD FLUSH

.

 THIS WILL ALSO HIGHLIGHT ANY FAULT WITH POWER 

SUPPLY

/

OUTLET 

(

IF MAINS POWERED

); 

 

I

F URINAL STILL DOES NOT FLUSH 

 CLEAN SOLENOID VALVE AND INLET FILTER

.

 

(

FINE PARTICLE 

DEBRIS

/

BUILD UP CAN PREVENT SOLENOID FROM OPENING AND CLOSING CORRECTLY

); 

 

I

F NEW INSTALLATION 

 

CHECK THAT FLUSH VALVE HAS BEEN INSTALLED CORRECTLY

,

 IN 

ACCORDANCE WITH THE INSTALLATION MANUAL

.

  IF NO LIGHTS ON SENSOR 

 RECHECK ALL 

CONNECTIONS AND ENSURE BATTERIES HAVE BEEN INSTALLED CORRECTLY

 

I

F RED LIGHT IS INDICATING AND YOU CAN HEAR THE SOLENOID CLICKING

,

 BUT NO WATER IS 

COMING OUT 

 CHECK WATER SUPPLY IS CORRECT AND WATER IS TURNED ON TO THE URINAL

;

 

 

 