ENSIM SENSORS EGW 201 Operating Manual Download Page 1

1

OPERATING

MANUEL

GUIDED RADAR (TDR)  TYPE LEVEL TRANSMITTER

EGW

Model  :

Model : 80-2021-001

Information in this manual is reviewed and completely reliable. Responsibility is not assumed due to any typing error.

Products in this manual are available only for information purpose and they may be changed without notice.

Important Notes:

Used Symbols :

 : Caution

: Note

: Disposal

Please read this manual carefully before installation of the 

Guided Radar (TRD) Type Level Transmitter

. User is responsible

for accidents and losses arising from failure to comply with the warnings in this manual.
In the event that 

Guided Radar (TRD) Type Level Transmitter

 is broken, take measures in order to prevent accidents and l

osses which can occur in its system.
There is not any fuse and circuit breaker on the instrument; they should have been added to the system by the user.
This manual should be stored in an easily accessible place for subsequent use.
The manufacturer's liability cannot exceed the purchase price of the device according to the law.
Do not make any modification on the instrument and do not try to repair it. Reparation should be made by authorized service staff.
Do not operate the system before making assembly in compliance with the assembly chart related to the instrument.
Products which do not contain label and serial number are considered to be excluded from the warranty scope.
The instrument's useful life, determined and announced by the ministry, is 10 years.

Table of Contents :

General Information...........................................................................................................................................................................2
Installation .........................................................................................................................................................................................4
Failure Detection..............................................................................................................................................................................23
Disassembly of Instrument ............................................................................................................................................................23
Service .............................................................................................................................................................................................23
Recalibration....................................................................................................................................................................................23
Repair................................................................................................................................................................................................23
Disposal ...........................................................................................................................................................................................23
Terms of Warranty ..........................................................................................................................................................................23
Terms of Return …………………………………………………………………………………………................................................…23

1.
2.
3.
4.
5.
6.
7.
8.
9.
10.

Models :

EGW 204, EGW 205
EGW 202, EGW 203
EGW 201, EGW 207
EGW 20S

Summary of Contents for EGW 201

Page 1: ...aker on the instrument they should have been added to the system by the user This manual should be stored in an easily accessible place for subsequent use The manufacturer s liability cannot exceed th...

Page 2: ...ion acc to EN 61326 1 Advantages In compact structure Easy to commission Durable mechanical structure High temperature versions are available Ambient Conditions Relative Humidity 5 98 RH Ambient tempe...

Page 3: ...age Sensitivity Repeatability Resolution Working Pressure Working Temperature Ambient Temperature Frequency Dielectric Constant E Response Time Sampling Frequency Power Consumption Supply Voltage Outp...

Page 4: ...e fluid in this case do not touch the transmitter your skin may be damaged 2 4 Installation For Mechanical Connections Use appropriate O ring or seal for sealing Make sure that its surface is clean an...

Page 5: ...l line of the sensor when filling through the silo or tank There is a blind area that cannot be measured by the sensors and known as the dead zone just below the antenna which does not exceed 5 cm acc...

Page 6: ...uxiliary signal plate with a diameter of 100 to 150 2 Auxiliary signal plate 3 Mounting head face and auxiliary plate face must be aligned Extension Rod and Boundary Ring For long mount hood extend th...

Page 7: ...he sleeve length should not be less than 100 mm The inner diameter of the sleeve must be at least 1 1 2 BSP Dalga k lavuzu t p ne montaj For boat setup and turbulent conditions you can mount the senso...

Page 8: ...incorrect measurements in case of faulty signals Installation Site Selection Correct Mount the sensor as far from the filling point as possible In terms of its lifetime use protectors to keep it away...

Page 9: ...y should be between 5 9mm with at least two wires and if necessary shielded type to protect it from electromagnetic fields 4 20mA analog output signal is also received through the same cable Two wire...

Page 10: ...between menus Sw tch between values Move the enlarge wave edge logo to the right Switch between steps ESC Back to the next upper menu Back to the main menu Switch to the graphic display OK Enter the m...

Page 11: ...t Skip processing Current output Parameter protection Settings eg Address type Information eg Distance record Number of restarts Information eg Production date Serial number Part number Version number...

Page 12: ...inction Time menu is displayed Press the OK key to jump from cursor to value You can set the suitable value between 0 99S Save the value with OK It is used to determine the range of variation of measu...

Page 13: ...4 Select the menu LCD Contrast with the key and enter with OK Make the setting with the keys Confirm with OK 5 Select the menu Language with the key and confirm with OK Available in English only C DI...

Page 14: ...t Calibration 2 Select the appropriate current and adjust the value according to the field condition Save the selection with OK 3 With enter the Calibration Confirm confirm with OK The setting above w...

Page 15: ...ith OK New adjustment can be added with Add 3 When using the Appoint option enter the appropriate distance value The signal is output at the distance determined by this setting Wait Direct Trend Appoi...

Page 16: ...our options Hold 22mA 20 5mA 3 5mA You can select the suitable one according to the field conditions Echo Lost Setting Jump operate Current output Parameter protect 4 20mA 20 4mA Current Direction 4 2...

Page 17: ...mber 000000000000000 Version number 307 204 H DIAGNOSIS J RECORD CURVE Echo Curve Record Linearization Securty Communication Diagnosis Distance record Maximum 0 140 m Minimum 0 139 m Reboot Count 00 0...

Page 18: ...Maximum Level C 20 mA This value with reference line max is the distance at the height of the liquid In this example it is 0 2 m In other words it is the 100 point where 20mA will be taken This point...

Page 19: ...1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 1 1 2 BSP 2 BSP 1 1 2 BSP 1 1 2 BSP 4 8 8 21 38 38 10 6 10 Max 32 m Max 6 m Max 2 m Max 4 m Max 4 m Max 6 m Max 32 m 155 155 155 155 155 155 155 MODEL CONNECTION BSP mm d...

Page 20: ...ART PTFE Insulation EXAMPLE HOUSING 8 Aluminum Housing B21x Std 702 Special x Plastic Housing B20p 103 IMMERSION LENGTH L mm 4 CERTIFICATE None 0 EN10204 3 1 Material Certification 1 Special x 4 20mA...

Page 21: ...ted Vibration can cause instability Do not remove the cover while energized Do not drop the transmitters and do not subject them to impacts Otherwise its characteristics may be affected The contact of...

Page 22: ...it to 0 and the output to 4 mA 5 The dielectric constant of the medium is too low 5 Replace the device with a high energy model 6 When measuring solid media the antenna is not perpendicular to the me...

Page 23: ...als user should send an open list related to damage or problem malfunction of the material to be returned or its operation in the different modification with the instrument If it is required to return...