High Temperature Refrigerated Air Dryers
Model QPHT 75/100/125
Unit Dimensions:
Length: 28”
Width: 18”
Height: 40”
Flow:
QPHT 75: 75 SCFM
QPHT 100: 100 SCFM
QPHT 125: 125 SCFM
Inlet Pressure:
175 PSIG (200 PSIG Maximum)
Ambient Temperature:
Minimum 55°F (13°C)
Maximum 100°F (38°C)
Inlet Temperature:
180°F (82°C) Maximum
Dew Pt. Temperature:
50°F±2° (10°C±1°)
Refrigerant H.P.:
QPHT 75: 1/2
QPHT 100: 3/4
QPHT 125: 3/4
Heat Exchanger Material:
Stainless Steel & Copper
Automatic Drain:
Installed
Refrigerant:
R-134A
Electrical Power Supply:
115V, 60Hz, 1 phase
Instrumentation:
ON/OFF switch
Power-on light
High temperature light
Refrigerant suction pressure gauge
Drain test button
Drain timer adjustment controls (2)
Maintenance & Adjustments
The ON/OFF switch holds a HIGH
TEMP light which will turn on if the
unit’s compressor system malfunctions.
If the red HIGH TEMP light on this
switch is illuminated, turn off and
unplug the unit for 15 minutes and
restart. If the light remains on after
restarting or it continues to turn on
afterwards, contact Quincy or your
distributor.
Periodic maintenance -
The following
procedures should be performed every
six months to insure that the air dryer
unit operates properly. These steps
should be performed more frequently
♦
♦
if either the air compressor or the air
dryer is exposed to air that is dirtier or
dustier than normal.
Clean optional ambient filter.
Clean optional coalescing oil filter
drain assembly
Replace optional coalescing oil filter
element
Clean moisture separator drain
assembly
Clean Particle Strainer
Clean condenser/air cooler coil.
a.
b.
c.
d.
e.
f.
Quincy Compressor-QPHT
11
Back to TOC