00-02-0796
- 24 -
2013-04-08
Fault Conversion
View/Edit the J1939 fault code version. Use the
Arrow
Keys
to move between Versions, and then touch
Enter
to
select a version.
NOTE:
There are four methods for converting fault
codes. The PowerView always looks for J1939-Version
4.
However, PowerView can be set to read one of three
other J1939 versions, if Version 4 is not
used/unavailable. Most ECU’s use Version 4, so
adjustment of this menu option is rarely required.
Upon receiving an unrecognizable fault, change to a
different J1939 Version in the list. If the fault SPN does not
change when the version is changed, the ECU generating
the fault is using
Fault Conversion Method 4
. If the SPN
number does change, but is still unrecognizable, try
changing to another unused J1939 Version and continue to
check the SPN number.