Section 40
00-02-0787
2015-03-23
~ 44 ~
Description
The
EMS PRO LITE
implements a MODBUS RTU style communications
protocol. The following describes the communications, and the register
and coil implementation for the
EMS PRO LITE
.
Protocol
The
EMS PRO LITE
controller will reply to MODBUS RTU
communications. This communications protocol uses RS232 or RS485
standards set to 9600-baud rate, no parity, eight (8) bits and one (1) stop
bit.
•
MODBUS® function code 03 - Read Holding Register
Status: Reads the binary contents of the holding
register in the
EMS PRO LITE
controller.
•
MODBUS® function code 06 - Preset Single Register:
Presets a value into a single holding register.
•
MODBUS® function code 16 - Preset Multiple
Registers: Presets values in a sequence of holding
registers.
Registers
Registers are adjustable or varying data locations within the controller
whose value is an integer value not just ON or OFF. They can represent
the system analog input for flow or pressure. The registers could be an
adjustable system parameter such as delay on start. The following is a
list of the registers that can be accessed. The maximum number of
registers that can be read at one time is 125. The starting address of the
registers is 40001.
NOTE: If a query is made to the
EMS PRO LITE
controller
beyond the published amount of registers, the
EMS PRO LITE
controller ignores the message as an invalid query.
Summary of Contents for Murphy EMS PRO LITE
Page 4: ......
Page 8: ...NOTES ...
Page 22: ...Section 40 00 02 0787 2015 03 23 14 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 60: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 61: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 62: ...THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 63: ......