Mounting
1.
Remove diffuser cover;
2.
Turn knobs to release and remove the gear tray. For emergency units, carefully unplug the green
indicator cable
(see picture right);
3.
Feed mains cables into fitting and mount luminaire base to ceiling using the mounting brackets;
4.
Hang gear tray onto luminaire base using the hanging clips;
5.
Connect mains wiring to terminal block
—
see
Wiring
section
;
6.
Emergency Models Only - plug green indicator cable into driver. Ensure correct polarity is maintained
by keeping the raised imprint & ink mark away from driver
(see picture right)
;
7.
Emergency Models Only - connect plug from battery cable to driver & record date of
commissioning on battery;
8.
Adjust microwave sensor settings as required
—
see
Microwave Sensor Settings
section.
9.
Secure the gear tray and diffuser onto the base.
Wiring
Standard model Emergency model
–
Non-switched Emergency model
–
switched
The emergency light
requires permanent
electrical supply and permanent
active must not be switched.
The permanent active
and
switched
active have to be energised for the
fitting to illuminate. If the switched
active is turned off then the battery
will charge but the fitting will not
illuminate in normal mode.
Emergency Models: Indicator & Simulation of Normal Power Supply Failure
Red LED
ON
= Charging
Red LED
OFF
= Battery fully charged
Green LED
ON
= Mains supply active
Green LED
OFF
= Mains supply failure
TEST BUTTON
Press & hold the Test button to simulate normal power supply failure. This will trigger emergency mode
switching LED supply from 240V supply to battery. Releasing the button will restore normal power to the luminaire.
2. & 6.
The raised imprint
and ink marking should be
facing away from the driver.
7.
Battery Plug
Permanent/ Unswitched
Active
Permanent/ Earth Neutral Switched
Unswitched Active
Active
Live Earth Neutral
Earth Neutral
Loop
If neither the green nor the red LED is on, check the mains wiring and ensure that the green indicator cable is connected in the correct polarity.
Continued next page
Vico
LED Batten
Installation Instructions
BL06xx, BL12xx, BL15xx models
NEW
:
Half-power option available by changing the dip-switch on the driver.
Maximum timer setting changed to 10 minutes
NOTE: ALL ELECTRICAL WORK MUST BE CARRIED OUT BY A LICENSED
ELECTRICIAN AS PER THE LATEST AS 3000 WIRING REGULATIONS.
WARNING: ALL MAINTENANCE, SUCH AS BATTERY CHANGE ON THIS LUMINAIRE, TO BE
PERFORMED BY A QUALIFIED PERSONNEL ONLY. DE-ENERGIZE ALL SUPPLIES BEFORE
MAINTENANCE.
•
This luminaire contains non-user replaceable lamps. Do not touch LEDs during installation or mainte-
nance or put gear tray facing downwards onto surface. Warranty void if LED damage found.
•
All entry points should be sealed properly to maintain the IP65 rating of the fitting. Warranty void if
water damage found.
It is the responsibility of the installer to ensure the following to avoid premature battery failure:
•
Emergency fittings should be installed within 3 months after purchase as extended storage may
shorten the battery life.
•
After connecting the battery, mains power should be supplied to the fitting within 7 days.