background image

3

5. Operation

Optimum performance and service life are achieved at a temperature 

of 20/25°C (68/77°F). The operating temperature range is as follows:
•  SBS XL 2V cells: -40°C to +50°C (-40°F to +122°F)
•  SBS XL 12V blocs: -40°C to +65°C (-40°F to +149°F).

5.1. Standby / Float Operation

Constant voltage chargers are recommended. The charging voltage should 

be set at the equivalent of 2.29Vpc at 20°C (68°F) or 2.275Vpc at 25°C (77°F). 
The recommended float voltage temperature compensation is:
•  +3mV per cell per °C below 20°C
•  –3mV per cell per °C above 20°C
The minimum charging voltage, at any temperature, is 2.21Vpc.

5.2. Charging Current

Due to the very low internal resistance PowerSafe

®

 SBS XL batteries will 

accept unlimited current during recharge but for cost and practical purposes 

in float applications where recharge time to repeat duty is not critical, the 

rectifier current can be limited to the load plus 0.1C

10

 Amps.

5.3. Discharging

Batteries must not be left in a discharged condition after supplying the load 

but must immediately return to recharge mode.
Failure to observe these conditions may result in greatly reduced service life.

Accidental deep discharging

For optimum operation the minimum voltage of the system should be 

related to the duty as follows:

In order to protect the battery it is advisable to have system monitoring 

and low voltage cut-out.
Deep discharge will produce a premature deterioration of the battery and 

a noticeable reduction in the life expectancy of the battery.

Effect of temperature

The temperature has an effect on the battery capacity. With increased 

operating temperature the capacity increases; likewise with decreasing 

temperature the capacity decreases.

6. Maintenance

In practice, the user usually specifies the maintenance schedule based 

on site criticality, location and manpower. However, the following may be 

used as a suggested maintenance schedule. Typically, the maintenance 

frequency for standard VRLA batteries is scheduled every 6 months. 

However, as a result of the increased design life inherent with the SBS XL 

range this interval frequency can be extended to deliver additional Total 

Cost of Ownership (TCO) benefit, particularly during the early period of 

service. As the battery approaches 80% of the intended service it would be 

beneficial to increase the frequency of maintenance.
Keep a logbook to record values, power outages, discharge tests, etc.
•  Measure the battery string voltage. If necessary, adjust the float voltage 

to the correct value.  

•  Measure individual bloc / cell voltages. After six months of operation, 

blocs/cells should be within 5% of the voltage value during float charge, 

as specified in chapter 5.1.

•  Check the ambient temperature in the immediate environment.
•  Inspect for contamination by dust, loose or corroded connections. 

If necessary, isolate the string/bloc/cell and clean with a damp soft cloth.  

Warning: Do NOT use any type of oil, solvent, detergent, petroleum-based 

solvent or ammonia solution to clean the battery containers or lids. These 

materials will cause permanent damage to the battery container and lid and 

will invalidate the warranty.

State of health monitoring

Typically a load test can be carried out once a year.

Capacity discharge testing is considered as the only true guide to state 

of health but can be complimented by the use of Ohmic measurement 

trending e.g. Conductance.

•  A discharge test should only be carried out on a fully charged battery.
•  For a new battery a discharge test should only be carried out after the 

commissioning charge is completed as specified in section 2.3.

Ensure the battery is fully recharged before capacity testing and always 

complete a full discharge test (partial discharges can lead to false 

assessment of state of health).
Best practice is to define the discharge test based on the application 

in terms of the load, autonomy or what is practical. The load and end of 

discharge voltage should be based on published performance literature. 

Depending on the operating temperature a compensation correction 

factor may be required.
Log individual bloc/cell voltage throughout the duration of the test  

at regular intervals.
Following the capacity test the battery should be fully recharged 

in accordance with instructions in section 5.

Ohmic measurements

The correct way to use Ohmic readings is as a trending tool over time to 

detect potentially weak or troublesome blocs/cells in a VRLA battery string 

in float in service. When the string is first installed and stabilized, a set of 

“initial” Ohmic readings should be taken. Since at this time there may still 

be some significant variations bloc to bloc/cell to cell in state of charge, 

separator acid content, recombination efficiency, etc. it is not unusual 

for these initial readings to be typically ± 50% of the mean. If some blocs/

cells exceed this, it would be judicious to equalize charge the string and 

do a capacity test.
After the string has been in service for about 6 months, the previous 

mentioned variations tend to normalise. At this point another set of Ohmic 

readings should be taken and used as the “baseline” readings. At this point, 

the blocs/cells should be typically within ± 30% of the average.
These individual “baseline” readings will serve as a reference for trending 

purposes for comparison to readings taken later in the battery’s life. 

On a yearly basis, Ohmic readings should be taken, recorded and compared 

to the baseline readings. If a bloc/cell or battery Ohmic reading varies more 

than 50% from the baseline value, the battery should be further evaluated 

to determine the cause. A performance or capacity test should be part of 

this evaluation.

7. Disposal

PowerSafe SBS XL batteries are recyclable. Scrap batteries must be 

packaged and transported in accordance with prevailing transportation 

rules and regulations.
Scrap batteries must be disposed of in compliance with local and national 

laws by a licensed or certified lead acid battery recycler.

Duty

Minimum end voltage

5 min ≤ t ≤ 1h

1.65V

1h ≤ t ≤ 5h

1.70V

5h ≤ t ≤ 8h

1.75V

8h ≤ t ≤ 20h

1.80V

Reviews: