background image

4

Avoid placing the battery in a hot place or in front of a window 

(no direct sunlight). Battery racks are recommended for proper 

installation.
The positive terminal is identified by a “+” symbol on each 

monobloc/cell. Install the batteries in accordance with the 

instructions and/or layout drawing, taking care to ensure 

correct terminal location and polarity.
Check that all contact surfaces are clean. Tighten terminal 

fasteners, taking care to use the correct torque loading. The 

fastener torque value is indicated on the product label.  Fit the 

covers supplied for protection against short circuit.
Follow the polarity to avoid short circuiting of monoblocs/cells. 

A loose connector can cause erratic battery performance and 

possible damage to the battery and/or personal injury. 

4.10 Commissioning Charge

The initial charge is extremely important as it will condition the 

battery service life. So, the battery must be fully recharged to 

ensure that it is in an optimum state of charge. 

Case 1:

 Using a constant voltage charger. Cells here will need 

to be recharged at a constant voltage of between 2.35 and 

2.40 Vpc (maximum) at 25°C for a minimum of 24 hours with a 

current limited to 0.01

C10

 Amps. Temperature compensation for 

charge voltage should be applied at the rates shown below:

Temperature

(ºC / ºF) 

Charge Voltage

(Vpc)

+10 / +50

2.44 

+20 / +68

2.40

+25 / +77

2.38

+30 / +96

2.36

+40 / +104

2.32

Case 2:

 With no external source available for recharging. 

Connect the battery to the solar panel regulator and leave at 

rest for 1 to 2 weeks. For this charge, set the regulator to the 

values outlined in the charging section..

4.11 End-of-charge reading 

The table hereafter gives an indication of the state of charge of 

blocs and cells from a reading of open circuit voltage.

State of Charge (%) 

Voltage

(Vpc)

100

2.17

90

2.15

80

2.12

70

2.10

5. Cyclic Operation

5.1 Cyclic Performance

The graph below shows cycling capability of PowerSafe SBS 

XC products:

Figure 2

5.2 Discharging 

Do not over-discharge the battery. This can be avoided by 

including a Low Voltage Disconnect (LVD) switch in the circuit 

or by disconnecting the battery from the load when the end 

discharge voltage is reached. As a rule, installations will be 

equipped with a regulator whose voltage threshold values will 

protect against deep discharge:

Discharge Time

(Hours)

10

120

240

Low Voltage 

Alarm

1.96Vpc

1.96Vpc

1.99Vpc

Disconnect 

Voltage (LVD) 

1.93Vpc

1.93Vpc

1.96Vpc

5.3 Charging

The high charge acceptance of the TPPL technology used in 

PowerSafe

®

 SBS

®

 XC is suited for applications which require 

a fast time to repeat duty. In such applications the voltage 

regulator should be set at 2.35Vpc to 2.40Vpc at 25°C.
Once fully charged the voltage can revert to float voltage with 

temperature compensation as required. There are a number 

of methods that can be utilised to control the recharge and 

determine, when using fast charge, that full state of charge is 

obtained such as Current Absorption and Ah Counting.
Based on current absorption, the recharge can be stopped 

when current being absorbed by the battery reaches       

0.01

C10

 Amps. At this point a timer can be set/activated to 

deliver an additional 1 hour of charge.

Typical Number of Cycles as a Function of Depth of Discharge

in Unreliable Grid Applications

Depth of Discharge (%)

Number of Cycles

10000

9000
8000
7000
6000
5000
4000
3000
2000
1000

0

10                 20                 30                 40                50                 60                 70

Reviews: