  Publication No: EN-GAZ-Standard-IOM 001 Dec 2012 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

During  the  charge  the  electrolyte  level 
and  temperature  should  be  observed 
(see  point  5.4).  The  electrolyte  level 
should never fall below the “MIN” mark. 
 

 

Battery  delivered  filled  and  charged 
and  stored  for  more  than  12  months

the battery should be charged for 15 hours 
at  the  rated  charging  current  0.2  I

A.

 

Approximately  4  hours  after  the  end  of 
charging,  the  electrolyte  level  should  be 
adjusted  to  the  upper  electrolyte  level 
mark “MAX” by using distilled or deionized 
water  in  accordance  with  IEC  60993.  For 
cells  with steel cases,  the  electrolyte  level 
should  be  adjusted  to  the  maximum  level 
according to the “Instruction for the control 
of  electrolyte  level”.

  During  the  charge 

the  electrolyte  level  and  temperature 
should be observed (see point 5.4). The 
electrolyte level should never fall below 
the “MIN” mark. 

 

Battery delivered filled and charged

/ a 5 

hour  charge  at  the  rated  charging  current 
0.2  I

A  must  be  carried  out  before  putting 

the battery into operation. Approximately 4 
hours  after  the  end  of  charging,  the 
electrolyte  level  should  be  adjusted  to  the 
upper  electrolyte  level  mark  “MAX”  by 
using  distilled  or  deionized  water  in 
accordance with IEC 60993. For cells with 
steel cases, the electrolyte level should be 
adjusted  to  the  maximum  level  according 
to  the  “Instruction  for  the  control  of 
electrolyte  level”. 

During  the  charge  the 

electrolyte 

level 

and 

temperature 

should be observed (see point 5.4). The 
electrolyte level should never fall below 
the “MIN” mark.

 

 

3.5.2 Commissioning with constant 
voltage 

 
If  the  charger´s  maximum  voltage  setting 
is  too  low  to  supply  constant  current  
charging,  divide  the  battery  into  two  parts 
that will be charged individually. 
 

Battery 

delivered 

unfilled 

and 

discharged 

/  after  a  period  of  5  hours 

from  filling  the  electrolyte,  the  battery 
should  be  charged  for  30  hours  at  the 
rated  charging  voltage  of  1.65  V/cell.  The 
current  limit  should  be  0.2  I

A  maximum. 

Approximately  4  hours  after  the  end  of 
charging,  the  electrolyte  level  should  be 
adjusted  to  the  upper  electrolyte  level 
mark  “MAX”  by  using  only  genuine 
electrolyte.  For  cells  with  steel  cases,  the 
electrolyte  level  should  be  adjusted  to  the 
maximum 

level 

according 

to 

the 

“Instruction  for  the  control  of  electrolyte 
level”.

 During the charge the electrolyte 

level  and  temperature  should  be 
observed 

(see 

point 

5.4). 

The 

electrolyte level should never fall below 
the “MIN” mark. 

 

 

Battery delivered filled and discharged

the  battery  should  be  charged  for  30 
hours at the rated charging voltage of 1.65 
V/cell.  The  current  limit  should  be  0.2 I

maximum. Approximately 4 hours after the 
end  of  charging,  the  electrolyte  level 
should 

be 

adjusted 

to 

the 

upper 

electrolyte  level  mark  “MAX”  by  using 
distilled  or  deionized  water  in  accordance 
with IEC 60993. For cells with steel cases, 
the electrolyte level should be adjusted to 
the  maximum  level  according  to  the 
“Instruction  for  the  control  of  electrolyte 
level.

  During  the  charge  the  electrolyte 

level  and  temperature  should  be 
observed 

(see 

point 

5.4). 

The 

electrolyte  level  should  never  fall 
below the “MIN” mark.

 

 
Battery  delivered  filled  and  charged 
and  stored  for  more  than  12  months

the battery should be charged for 30 hours 
at  the  rated  charging  voltage  of  1.65 
V/cell.  The  current  limit  should  be  0.2  I

maximum. Approximately 4 hours after the 
end  of  charging,  the  electrolyte  level 
should be adjusted to the upper electrolyte 
level  mark  “MAX”  by  using  distilled  or 
deionized  water  in  accordance  with  IEC 
60993.  For  cells  with  steel  cases,  the 
electrolyte  level  should  be  adjusted  to  the 
maximum 

level 

according 

to 

the 

“Instruction  for  the  control  of  electrolyte 
level”.

 During the charge the electrolyte 

level  and  temperature  should  be 
observed 

(see 

point 

5.4). 

The 

electrolyte level should never fall below 
the “MIN” mark. 
 

 

Battery  delivered  filled  and  charged

/  a 

10  hour  charge  at  the  rated  charging 
voltage  of  1.65  V/cell  must  be  carried  out 
before  putting  the  battery  into  operation. 
The  current  limit  should  be  0.2  I

maximum. Approximately 4 hours after the 
end  of  charging,  the  electrolyte  level 
should be adjusted to the upper electrolyte 
level  mark  “MAX”  by  using  distilled  or 
deionized  water  in  accordance  with  IEC 
60993.  For  cells  with  steel  cases,  the 
electrolyte  level  should  be  adjusted  to  the 
maximum 

level 

according 

to 

the 

“Instruction  for  the  control  of  electrolyte 
level”. 

During the charge the electrolyte 

level  and  temperature  should  be 
observed 

(see 

point 

5.4). 

The 

electrolyte level should never fall below 
the “MIN” mark. 

 

4. Charging in Operation 

 

4.1 Continous battery power supply

 

(with occasional battery discharge)

 

 

Recommended 

charging 

voltage 

for 

ambient temper 20 °C to + 25 °C. 
Do not remove the vent caps during float-, 
boost  charge  and  buffer  operation.  The 
current limit should be 0.3 I

A maximum in 

general. 

 

4.1.2 Two level charge 

 
Floating:  

1.40 – 1.42 V/cell 

Boost charge:  

1.55 – 1.70 V/cell 

 
A high voltage will increase the speed and 
efficiency of recharging the battery. 
 

4.1.3 Single level charge 

 
1.45 – 1.50 V/cell 
 

4.2 Buffer operation 

 
Where  the  load  exceeds  the  charger 
rating. 
 
1.45 – 1.55 V/cell  
 

5. Periodic Maintenance 

 

The battery must be kept clean using only 
water. Do not use a wire brush or solvents 
of  any  kind.  Vent  caps  can  be  rinsed  in 
clean water if necessary but must be dried 
before using them again.  
 
Check  regularly  (approximately  every  6 
months)  that  all  connectors,  nuts  and 
screws are tightly fastened. Defective vent 
caps  and  seals  should  be  replaced.  All 
metal  parts  of  the  battery  should  be 
corrosion-protected  by  coating  with  a  thin 
layer  of  anti-corrosion  grease. 

Do  not 

coat  any  plastic  part  of  the  battery,  for 
example cell cases!

 

 
Check the charging voltage. If a battery is 
parallel  connected  it  is  important  that  the 
recommended  charging  voltage  remains 
unchanged.  The  charging  current  in  the 
strings should also be checked to ensure it 
is equal. These checks have to be carried 
out  once  a  year.  High  water  consumption 
of  the  battery  is  usually  caused  by 
improper voltage setting of the charger. 

 

5.1 Equalizing charge 

 
It  is  recommended  to  carry  out  an 
equalizing charge once a year to maintain 
capacity and to stabilize the voltage levels 
of the cells. The equalizing charge can be 
carried  out  for  15  hours  at  0.2  I

A  or  with 

the boost charging stage in conformity with 
the  characteristic  curve  of  the  available 
charging  equipment.  The  electrolyte  level 
must  be  checked  after  an  equalizing 
charge. 

 

In  order  to  equalize  the  floating  derating 
effect,  it  is  recommended  to  charge  the 
battery  once  a  year  for  15  hours  at  the 
rated  charging  current  0.2  I

A.  Then 

discharge  the  battery  down  to  1.0  V/cell 
and  charge  again  for  8  hours  at  the  rated 
charging current 0.2 I

A. 

 