 PV Bloc batteries must be given a refreshing charge:

  a.    when maximum storage time is reached, or
  b.    when the OCV approaches 2.10Volts/cell whichever occurs 

fi

 rst

1.3 Freshening Charge

 

The refresh charge should be conducted using constant voltage (adjusted to the temperature) eg. 2.27Vpc at 20-25°C 
with 0.1 C

10  

Amps current limit for a minimum period of 96h.

1.4 Commissioning

Installation & ventilation

The electrical protective measures and the accommodation and ventilation of the battery installation must be in 
accordance with the applicable “local” national standards, rules and regulations.
Low ventilation requirement according to EN 50272-2.

The battery should be installed in a clean, dry area.

Avoid placing the battery in a hot place or in front of a window. 

Check that all terminals contact surfaces are clean. Connect PV bloc with dedicated connectors following the wiring 
circuit.

A loose connector can cause trouble in adjusting the system, erratic battery performance, and possible damage to the 
battery and/or personal injury.

Commissioning

The initial charge is extremely important as it will condition the battery service life. So the battery must be fully recharged 
to ensure that it is in an optimum state of charge.

Case 1:

 Using a constant voltage charger. Cells here will need to be recharged at a constant voltage of between 2.35 

and 2.40 Vpc at 25°C for a minimum of 48h and a maximum of 72h with a current limited to 0.10C

10

.

Case 2:

 With no external source available for recharging. Connect the battery to the solar panel regulator and leave 

at rest for 1 to 2 weeks. For this charge, set the regulator to the following values:

TºC

Voltage per cell

Low charge-restart voltage

  0 to 20ºC

2.30V

20 to 40ºC

2.30V

High charge-disconnect 

voltage

  0 to 20ºC

2.50V

20 to 40ºC

2.45V

End-of-charge

 

The battery is charged once open-circuit voltage (OCV) readings after 24h of rest are in conformity with the values 
shown on the above table. Each cell must register less than a 2% divergence from the average OCV reading.

1.5 Disposal

Lead acid PowerSafe

®

 PV Bloc batteries are recyclable. End of life batteries must be packaged and transported 

according to prevailing transportation rules and regulations. End of life batteries must be disposed of in compliance 
with local and national laws by a licensed battery recycler.

Summary of Contents for PowerSafe PV Bloc

Page 1: ...Sustainable solutions PowerSafe PV Bloc Operation Guide for Solar Applications...

Page 2: ...very corrosive When working with sulphuric acid always wear protective clothing and glasses Exposed metal parts of the battery always carry a voltage and are electrically live risk of short circuits...

Page 3: ...of Temperature On capacity Correction factors of the capacity according to the temperature are shown in the curve below If the temperature is other than 25 C the correction factors must be applied to...

Page 4: ...perature range of 20 C to 45 C Humidity 90 The self discharge rate of PV Bloc batteries is a function of the temperature Temperature 25 C 30 C 40 C Monthly self discharge rate 3 4 8 PowerSafe PV Bloc...

Page 5: ...missioning The initial charge is extremely important as it will condition the battery service life So the battery must be fully recharged to ensure that it is in an optimum state of charge Case 1 Usin...

Page 6: ...109 121 344 13 5 172 6 8 276 10 9 38 0 83 7 1865 6 62 6 PVB 225 6 195 225 244 9 6 190 10 6 270 10 6 31 0 68 3 2048 3 11 Notes The electrical values shown in the table relate to perfomance from a full...

Page 7: ...30V 2 25V High recharge disconnect voltage Vpc 2 55V 2 45V 2 40V 2 35V 3 MAINTENANCE CHECKS DATA RECORDING PowerSafe PV blocs are VRLA batteries and do not have to be topped up Do not open the valve O...