background image

5

www.enersys-emea.com

• the terminals, connecting straps and fasteners are adequately

coated with lanolised petroleum jelly.

Front covers have slots located in each corner. Use the screws
supplied to fasten the covers onto the captive nuts located in the
front face of the stand frames.

8. Commissioning Charge

It is recommended that chargers are of the constant voltage
type. The output characteristic should give an applied charge
voltage of 2.28±0.01Vpc (at 20°C) or temperature compensated
equivalent (see section 9.2.1) with a minimum output current
expressed numerically in amperes as 10% of the 10 hour
capacity rating of the battery.

The commissioning charge should be carried out, without any
other load being connected to the charger, as follows:

• connect charger positive output to battery positive terminal,

charger negative output to battery negative terminal.

• switch on and charge continuously until the current flow into

the battery has fallen to a minimum and stabilised to remain
relatively constant over 3 consecutive hourly readings.

If it is not possible to determine the current, the battery may be
assumed to be fully charged after a minimum continuous charge
period of 6 days.

The battery temperature should be monitored during the
commissioning charge. If it exceeds 40°C the charge must be
terminated immediately; it should not be continued until the
temperature has fallen to 32°C.

NB: If the battery is to be subjected to a site acceptance test
before going into service, this must be carried out in the period
between completion of the commissioning charge and the
introduction of operating load on the system.

On completion of the commissioning charge (and, if required,
site acceptance test and subsequent recharge) the load circuit
can be introduced on to the system and the battery maintained
in the normal float charge mode.

9. Operation

9.1 Chargers

Constant voltage chargers only are recommended for normal
continuous operation.

9.2 Charging

9.2.1 Applied voltage level for normal float charge

For all normal operating conditions, and particularly where the
battery is maintained fully charged continuously in parallel with
the charger and load circuit, it is recommended that a voltage
level equivalent to 2.28±0.01Vpc (at 20°C) is applied to the
battery terminals.

Where the mean operating temperature is not 20°C, the applied
voltage level should be adjusted as follows:

• 2.28Vpc + 0.003V per cell per °C below 20°C

• 2.28Vpc - 0.003V per cell per °C above 20°C

To prevent the possibility of undercharge, it is important that the
applied charge voltage does not drop below the minimum
recommended value for the operating temperature.

Similarly, to prevent the possibility of overcharge, any excursion
of 'battery voltage' above the maximum recommended value for
more than one minute should either be alarmed or cause
immediate termination of the charge (except under controlled
elevated voltage conditions described in section 9.2.2).

This level of applied voltage is recommended for both the
Refresher Charge (section 6) and Commissioning Charge (section
8) procedures or to recharge the battery following a discharge.

Under these conditions, it will typically require a period of
continuous charge in excess of 72 hours to fully recharge a battery
which has previously been discharged to the extent of its 10 hour
capacity. The battery will be fully recharged when the charge
current has reduced to a very low value and has remained
reasonably constant for 3 consecutive hourly readings. 
At 2.28±0.01Vpc (at 20°C), this value of end of charge current 
will typically be in the region of 0.5mA per Ah of the rated 10 hour
capacity.

9.2.2 Applied voltage level for faster recharge

Recharge time can be reduced by increasing the level of applied
charge voltage.

If the time available for recharge is constrained, then the battery
may be recharged by applying a maximum constant voltage level
of 2.35 Volts per cell. However, using this charging regime:

• will result in a reduced service life if used more than once per

month.

• requires the charge current to be limited to a value expressed

numerically in Amperes to 10% of the 10 hour capacity rating of
the battery (e.g. 85 Amps for battery of DDm 85-21).

• requires the charge to be terminated when the charge current

stabilises; typically this will be in the region of 3mA per Ah of the
rated 10 hour capacity rating of the battery.

If necessary, the Refresher Charge procedure (section 6) may be
carried out using this elevated voltage level; however, the charge
must be terminated after a maximum continuous charge period of
8 hours. Similarly, the Commissioning Charge procedure (section
8) may be carried out using 2.35 Volts per cell for a maximum
continuous charge period of 12 hours.

However, neither of these 2 alternative procedures should be
attempted without first referring to EnerSys

®

for precise

instructions.

9.2.3 Equalising charge

Under normal conditions an equalising charge is not required.
However, in some circumstances, a maximum continuous charge
period of 12 hours using 2.35 Volts per cell or an extended period
of carefully controlled low value constant current charge may
prove beneficial.

EnerSys must be contacted for advice if an equalising charge is to
be undertaken.

9.2.4 Charge current

For optimum charge efficiency, the recommended charge current
to the battery should be a value expressed numerically in
Amperes equivalent to 10% of the 10 hour capacity rating of the
battery.

However, PowerSafe

®

DDm batteries will accept higher values of

charge current without damage providing that the applied charge
voltage does not exceed the normal float charge voltage level of
2.28±0.01Vpc (at 20°C) or temperature compensated equivalent
(see section 9.2.1).

It is important that the 10% C

10

Amperes current becomes a

maximum value when applying any value of elevated voltage
between 2.29 Volts per cell and 2.35 Volts per cell.

Summary of Contents for PowerSafe 2DDM50-09

Page 1: ...RESERVE POWER Installation Operation Maintenance Manual Conventional Anti Shock Stand Configurations...

Page 2: ...into contact with acid Gases Batteries can give off explosive gasses Keep sparks flames and lighted cigarettes away from the battery Isolate the battery circuit before connecting or disconnecting the...

Page 3: ...le performance They are designed to be installed in the horizontal position that affords simplified front access installation and maintenance even in the most difficult locations 4 Receiving Unpacking...

Page 4: ...along the front face of the runner to allow clamping plates to be fitted over the flanges and edge of the cell lid of adjacent modules see fig 12 2 NB The clamping plates must be fitted before cell c...

Page 5: ...nation of the charge except under controlled elevated voltage conditions described in section 9 2 2 This level of applied voltage is recommended for both the Refresher Charge section 6 and Commissioni...

Page 6: ...erting to normal operation ensure that the battery charging voltage is correct Measure and record the ambient temperature in the vicinity of the battery and all cell voltages Following a commissioning...

Page 7: ...12 13 14 15 16 7 www enersys emea com Frame Runner Terminal rail Insulating nut cap short M8 x 80 HX HD bolt M8 plain washer M8 spring washer M8 nut Insulating nut cap long M8 x 70 socket HD bolt M8...

Page 8: ...85 33 C SUB5872 SUB5876 SUB5887 SUB5886 SUB5751 DDM100 21 B SUB5872 SUB5876 SUB5889 SUB5751 DDM100 25 B SUB5872 SUB5876 SUB5890 SUB5751 DDM100 27 B SUB5872 SUB5876 SUB5891 SUB5751 DDM100 33 C SUB5872...

Page 9: ...C SUB5732 SUB5738 SUB5744 SUB5743 SUB5751 DDM100 21 B SUB5732 SUB5738 SUB5746 SUB5751 DDM100 25 B SUB5732 SUB5738 SUB5747 SUB5751 DDM100 27 B SUB5732 SUB5738 SUB5748 SUB5751 DDM100 33 C SUB5732 SUB57...

Page 10: ...93 94 95 96 97 98 99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125 126 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 14...

Page 11: ...11 www enersys emea com Notes...

Page 12: ...emarks and logos are the property of EnerSys and its affiliates unless otherwise noted EnerSys World Headquarters 2366 Bernville Road Reading PA 19605 USA Tel 1 610 208 1991 1 800 538 3627 Fax 1 610 3...

Reviews: