Installation
900-0258-01-00 Rev A
19
8. Lightly brush the terminal contact surface areas with a brass bristle brush or the
equivalent, then coat with dielectric grease such as NO-OX-ID or NCP-2. Carefully
install short bus bars using M10 bolts so that batteries are connected in series. Torque
bolts to 28.1 to 33.8
N
⋅
m
(287 to 344 kgf
⋅
cm) or 531 Lbf
⋅
in, then place protection covers
over each bus bar.
Figure 12 Install Short Bus Bars and Insulating Covers
Insulating Plastic
Protection Cover
Short Bus Bars