background image

The electrolyte temperature of batteries should be at least 

+10°C before charging otherwise a full charge will not be 

achieved. A charge is finished when the specific gravity of the 

electrolyte and the battery voltage have remained constant for 

2 hours.

 2.3  Equalising charge

Equalising charges are used to safeguard the life of the 

battery and to maintain its capacity. They are necessary after 

deep discharges, repeated incomplete recharges and charges 

to an IU characteristic curve. Equalising charges are carried 

out following normal charging. The charging current must 

not exceed 5A/100Ah of rated capacity (see section 2.2). 

 

Pay attention to the temperature!

 2.4  Temperature

An electrolyte temperature of 30°C is specified as the rated 

temperature. Higher temperatures shorten the life of the 

battery, lower temperatures reduce the capacity available. 

55°C is the upper temperature limit and is not acceptable as 

an operating temperature.

 2.5  Electrolyte

The rated specific gravity (S. G.) of the electrolyte is related to 

a temperature of 30°C and the nominal electrolyte level in the 

cell in fully charged condition.

Higher temperatures reduce the specified gravity of the 

electrolyte, lower temperatures increase it. The temperature 

correction factor is -0.0007kg/l per °C, e.g. an electrolyte 

specific gravity of 1.28kg/l at 45°C corresponds to an S.G. of 

1.29kg/l at 30°C. The electrolyte must conform to the purity 

regulations in IEC 62877-2: 2016.

  3.     Maintenance
 3.1  Daily

Charge the battery after every discharge. Oerlikon Water 

 

Less

®

 with electrolyte circulation: at the end of charge the 

electrolyte level sensor should be checked (see table 3.1.1) 

and if necessary topped up to the specified level with purified 

water (according IEC 62877-1: 2016).

NO WATERING IN THE FIRST 10 CYCLES.

 3.1.1 Filling level sensors

The LED of the electrolyte level sensor should be observed 

daily.

ELECTROLYTE LEvEL INdICATOR

TYPE

(2 - 3)... PzMB

white housing

Green 

 electrolyte level is OK

No indication 

 water topping up should 

be carried out

TYPE

(2 - 10)... PzM and (4 - 11)... PzMB

blue housing

Green flashing 

 electrolyte level is OK

Green/red flashing 

 safety cycle limit 

countdown

Red flashing 

 water topping up should be 

carried out

do not top up the cells even when electrolyte level sensor 

shows a red blinking LEd during first 10 cycles.

The electrolyte level checking has to be performed after low 

level detection of the sensor or after water topping up interval 

(see "Water refilling system") Check the electrolyte level 

(visual inspection by opening the vent plug or by the position 

of the float indicator of the Aquamatic plug) and top-up with 

demineralised water at the end of the charge. Since the 

display always refers to a selected reference cell, please also 

pay attention to the additional instructions under section 3.3.

 3.2  Weekly

Visual inspection after recharging for signs of dirt and 

mechanical damage to all component parts of the battery, pay 

particular attention to the battery charging plugs and cables. 

By special applications with charge with a IU characteristic 

curve an equalising charge must be carried out (see sections 

2.3 and 7.).

 3.3  Monthly

At the end of the charge the voltages of all cells should be 

measured with the charger switched on, and recorded. 

After charging has been completed, the electrolyte density, 

electrolyte temperature as well as the filling level (when filling 

level sensors are used) of all cells are to be measured and 

recorded. If significant changes from earlier measurements 

or differences between the cells are found further testing and 

maintenance by the service department should be requested.

This should be done following a complete charge and 

minimum of 2 hours rest time.

Measure and record:

•  total voltage

•  voltage per cell

•  if the voltage readings are irregular, also check

  the S.G. of each cell

(see section 7.)

 3.4  Quarterly

Follow section 7.

 3.5  Annually

In accordance with EN 1175-1 at least once per year, the 

insulation resistance of the truck and the battery must be 

checked by an electrical specialist. The tests on the insulation 

resistance of the battery must be conducted in accordance 

with EN 1987-1. The insulation resistance of the battery 

thus determined must not be below a value of 50

Ω

 per volt 

of nominal voltage, in compliance with EN 62485-3. For 

 

batteries up to 20V nominal voltage the minimum value is 1000

Ω

.

Proceed to the quarterly maintenance, including the 

measurement of electrolyte S.G. at the end of charge.

For batteries equipped with optional electrolyte circulation 

system, the filter of the air pump has to be checked during the 

annual maintenance and eventually to be cleaned or replaced. 

Earlier replacement of the filter is necessary if for undefined 

reasons (no leaks in the air pipes) the defect signal of the 

electrolyte circulation system on the charger or on the battery 

(on DC air pump or remote signal) is illuminated. During the 

annual maintenance, check the correct operation of the air 

pump.

 4.  Care of the battery

The battery should always be kept clean and dry to prevent 

tracking currents. Cleaning must be done in accordance with 

the ZVEI code of practice “The Cleaning of Vehicle Traction 

batteries”.

Any liquid in the battery tray must be extracted and disposed 

of in the prescribed manner. Damage to the insulation of the 

tray should be repaired after cleaning, to ensure that the 

insulation value complies with EN 62485-3 and to prevent tray 

corrosion. If it is necessary to remove cells, it is best to call in 

our service department for this.

Never use (apply) mineral grease on the battery, the 

sealing material of the terminal is incompatible and it can 

be permanently damaged. If it's necessary, use (apply) the 

silicone grease with TPFE.

  5.   Storage

If batteries are taken out of service for a lengthy period, they 

should be stored in the fully charged condition in a dry, frost-

free room. To ensure the battery is always ready for use a 

choice of charging methods can be made:

1. a monthly equalising charge as in section 2.3, or

2. float charging at a charging voltage of 2.27V x the number 

  of cells.

The storage time should be taken into account when 

considering the life of the battery.

  6.   Malfunctions

If malfunctions are found on the battery or the charger our 

service department should be called in without delay. The 

measurements taken in section 3.3 will facilitate fault finding 

and their elimination.

A service contract with us will make it easier to detect and 

correct faults in good time.

Reviews: