1. Application

The water refilling system is used to automatically maintain
the nominal electrolyte levels. 
The charging gasses escape through the vent on each cell.

NO WATERING IN THE FIRST 10 CYCLES

2. Function

A  valve  and  a  float  together  control  the  topping  up  process
and  maintain  the  correct  water  level  in  each  dell.  The  valve
allows the flow of water into each cell and the float closes the
valve when the correct water level has been reached.
For  fault-free  operation  of  the  water  refilling  system,  please
note the instructions below: 

2.1 Manual or automatic connection

The battery should be topped up shortly before completion
of  a  full  charge,  as  at  this  point  the  battery  has  reached  a
defined operational state resulting in satisfactory electrolyte
mixing.

Filling  takes  place  when  the  connector  (7)  from  the

tank is connected to the coupling (6) on the battery. 

2.1.1

If manual connection is used the battery should only
be connected to the filling system once a week.

2.1.2

If  automatic  coupling  is  used  (with  a  magnetic  valve
controlled  by  the  charging  apparatus)  the  charger
main switch selects the correct moment for filling. 
Note:  In  this  case  we  recommend  a  water  refilling 
at    least  once  a  week  to  ensure  the  right  level  of  the
electrolyte.

2.1.3

In  multiple  shift  and  warm  ambient  temperature 
operations,  it  may  be  necessary  to  have  shorter 
topping up intervals.

2.2 Filling time

Filling  time  depends  on  the  utilisation  rate  and  the 
corresponding battery temperature.  Generally speaking, the
top up process takes a few  minutes and can vary according
to the battery range; after this, if manual filling is being used,
the water supply to the battery should be turned off.

2.3 Working pressure

The water refilling system should be installed in such a way
that a water pressure of 0.2 to 0.6 bar is obtained (with at least
2 m height difference between the upper edge of the battery
and  the  lower  edge  of  the  tank).  Any  deviation  from  this
means that the system will not function properly. 

2.4 Purity

The  topping  up  water  must  be  purified.    The  water  used  to
refill  the  batteries  must  have  a  conductance  of  not  more 
than 30 µS/ cm. The tank and pipes must be cleaned before 
operating the system.

2.5 Pipe system on the battery 

The  pipe  system  to  the  individual  battery  cells  must  follow
the battery’s electrical circuit.  This reduces the risk of current
leakage  in  the  presence  of  electrolytic  gas  causing  an 
explosion (DIN EN 50272-3). A maximum of 20 cells may be
connected in a series.
The system should not be modified in any way.

2.6 Working temperature

In  winter,  batteries  fitted  with  Aquamatic  should  only  be 
charged or refilled in a room temperature above 0°C. 

2.7 Flow control

A  flow  indicator  built  into  the  water  supply  pipe  to  the 
battery  monitors  the  filling  process.  During  filling  the  water
flow  causes  the  built-in  disc  in  the  flow  indicator  to  turn.
When all the plugs are closed the disc stops, indicating that
the filling process is complete.

OPTIONS
Aquamatic water refilling system (optional accessory)

1. tank

2. outflow connector with ball valve

3. plug with magnetic valve

4. plug with ball valve

5. flow control

6. coupling

7. connector

8. battery charger

9. charger main switch

1

2

3

4

5

7

6

8

9