3. Operation

EN 50272-3 “Safety requirements for secondary batteries and
battery installations Part 3: Traction batteries” is the standard
which applies to the operation traction batteries in industrial
trucks.

3.1. Discharge

Ventilation openings must not be sealed or covered. Electrical
connections (e.g. plugs) must only be connected or dis-
connected in the open circuit condition. To achieve the
optimum life for the battery, operating discharges of more
than 80% of the rated capacity must be avoided (deep
discharge). They reduce the battery service life. To measure
the state of discharge use only the battery manufacturer’s
recommended discharge indicators (imperative presence of a
discharge limiter with an energy cut-off at 1.83 vpc operating
voltage at 80% DOD C

5

, when the recharging time is 12 hours,

and 1.87 vpc at 60% DOD C

5

when the recharging time is

8 hours). Discharged batteries must be recharged and never
be left in a discharged state for a long time.
Oerlikon

®

Evolution batteries can be used in normal duty

applications for a maximum 6 days per week.
Avoid applications where:

no rest time is available allowing the battery to cool

battery duty leads to a high increase of temperature during
operation.

3.2. Charging

A full charge shall be carried out every working day.
The charging time for a 80% discharged battery shall be
12 hours, or 8 hours for a 60% discharged battery with the
appropriately assigned Oerlikon HF charger.
After any changing of cables on the charger, our technician
must visit the site to check the charger.
Oerlikon Evolution batteries have a low gas emission.
Nevertheless, when charging, proper provision shall be made
for venting of the charging gases (EN 50272-3). Battery con-
tainer lids and the covers of battery compartments shall be
opened or removed. With the charger switched off connect
the battery, ensuring that the polarity is correct. (Positive to
positive, negative to negative). Now switch on the charger.

3.3. Equalising charge

Equalising charges are used to optimise the life of the battery
and to maintain its capacity. A unique equalisation charge is
automatically carried out weekly 8 hours after the end of the
charge with a Oerlikon HF charger.

4. Battery life

The optimum lifetime of the battery depends on the
operating conditions (temperature and depth of discharge)

4.1. Temperature

The temperature range of use for the battery is b5°C
and + 35°C. Any use outside of this range shall be approved
by a Oerlikon service technician. Optimal battery life is obtai-
ned for a battery temperature of 25-30°C High temperatures
reduce battery life according to IEC 1431 technical report,
lower temperatures reduce the capacity available.

5. Maintenance

The electrolyte is immobilised in a gel. The density of the
electrolyte cannot be measured.

Never refill with water!

Never remove the safety valve from the cell

In case of accidental damage of the valve, contact our After
Sales Service for replacement.

The battery should always be kept clean and dry to prevent
current leakage. Any liquid in the battery tray shall be
extracted. Damage to the insulation of the tray should be
repaired after cleaning, to ensure a good insulation and to
prevent tray corrosion. If it is necessary to remove cells it is
best to call in our service department for this.

5.1. Daily

Check that the plugs and sockets are in good condition.

5.2. Monthly / quarterly

Carry out end of charge voltage readings at C

5

/100,

measure and record:

the voltage of the battery

the voltages of each cell

If significant changes from earlier measurements or differen-
ces between the cells or bloc batteries are found, please
contact Oerlikon Service.

If the discharge time of the battery is not sufficient, check:

That the work required is compatible with the battery
capacity

The settings of the charger

The settings of the discharge limiter.

5.3. Annually or biannually

Internal dust removal from the charger.
Check with attention:

the state of the plugs: be sure to have a good contact
between the plugs without trace of overheating.

the state of the output cables.

If you check the torque loading, you shall use a torque wrench
with respect of recommended value: 25+/- 2 Nm.
In accordance with EN 1175-1 at least once per year, the
insulation resistance of the truck and the battery must be
checked by an electrical specialist.
The tests on the insulation resistance of the battery shall
be conducted in accordance with EN 1987-1.
The insulation resistance of the battery thus determined must
not be below a value of 50

per Volt of nominal voltage, in

compliance with EN 50272-3. For batteries up to 20 V nominal
voltage the minimum value is 1000

.

6. Storage

If batteries are taken out of service for a lengthy period they
should be stored, disconnected from the truck, in the fully
charged condition in a dry, frost-free room.
Batteries shall be recharged after a maximum storage time of:

2 months at 30°C

3 months at 20°C

Effect a recharge before putting the battery into service. A
monthly refreshing charge is recommended. The storage
time should be taken into account when considering the life
of the battery. Never leave a battery connected to a truck for
a long time.
Storage at open circuit is not allowed when in discharged
state.

7. Malfunctions

If malfunctions are found on the battery or the charger our
service department should be called without delay. A service
contract with us makes it easier to detect and correct faults in
good time.