background image

ENGLISH

SAFETY INSTRUCTIONS

GOALS OF THIS MANUAL

This manual is aimed at any authorized personnel wanting
to use a single phase

POWERTECH IQ 

charger to recharge

lead acid motive power batteries (vented, XFC FLEX, Gel or
WF200 ranges)
This manual contains information on:

Charger functionality.

Use and setting of charger parameters.

Technical specifications of the Powertech IQ chargers.

EnerSys intends to provide clear and simple information 
in this manual, and assumes no responsibility for misunder-
standing or improper interpretation of the information.
The owner of the equipment is required to preserve this
manual during the life of the equipment and to transfer said
manual to any subsequent purchaser.

WARRANTY

Warranty is offered by the  manufacturer based on local 
regulations. Please contact your local distributor for further
information.

RECOMMENDATIONS

Recommendations for safe operation

This  manual should be carefully read, prior to using the
equipment, by anyone intending to use the charger. The
Powertech IQ:

Must not have its air circulation impaired in any way, 
primarily around the air inlet areas. Dust accumulation
must be removed every six months.

Must be used within its protection norms, and never 
be directly in contact with water. 

Must be used only within the temperature range 
specified in the technical specifications 

Must not be installed on a surface subject to high 
vibration levels (proximity of motors, compressors, etc.).

Must not be installed close to the batteries in order to
avoid any 
gassing that could damage it prematurely.

Must not be installed in arduous environments such as:
•  Harbour applications (saline air),
•  Close to cold stores
•  External locations with exposure to wind and rain.

Operator safety

All proper precautions must be observed when the 
equipment is used in areas where accidents are possible.
Ensure proper ventilation when the charger is used with 
lead-acid batteries, due to gassing. Never disconnect the 
battery during the charging process.

General warnings

Requirements for use:

The equipment must be properly grounded (earthed).

The input voltage must match the charger requirements.

The battery voltage must match the charger’s 
capabilities.

The battery capacity is within the charger’s range.

ELECTRICAL SAFETY

Safety regulations and requirements must be observed.

Safety devices installed on the electrical supply to the 
chargers must be of the proper type and rating. It is 
important to ensure that only fuses of the proper 
capacity be used, should they need to be replaced. 

This charger meets the Class 1 Electrical Safety requirements, and therefore needs to be properly grounded during instal la tion. It must be connected to a power supply equipped with a ground cable, and the ground connection should be as short as possible. 

The equipment must be totally disconnected from all power
sources (mains supply and battery) before it can be opened
for inspection or servicing. The battery can only be discon-
nected 

after

the STOP/START button has been pushed.

Access to the inside of the charger should be restricted to
authorized maintenance personnel. 

Please consult a qualified factory representative about any
problems or questions related to the installation of this
unit.

LIMITS OF USE

This charger is designed to be used in a sheltered area. 
It is designed exclusively to recharge lead batteries in an
industrial environment. 

PRODUCT  RECYCLING - DESTRUCTION

When this charger becomes obsolete, it can be recycled 
or destroyed by authorized facilities. Local regulations will
prevail and must be followed.

MODIFICATIONS AND IMPROVEMENTS

EnerSys reserves the right, at any time, to modify or 
improve its products, without any obligation to update 
this product or this manual accordingly. 

RECEIVING - STORAGE

Upon receipt, please inspect visually the exterior of the 
charger for any physical damage. If necessary, proceed 
within 24 hours with the usual claims procedure with the
transport company.

If the charger is to be stored before use, it should remain 
in the original packaging, carefully closed. Store in a clean,
dry area at a moderate temperature (0 °C to +40 °C). If the
equipment is stored at a temperature below 15°C, it must 
be gradually (24 hours) restored to operating temperature
before use, to prevent the risk of condensation that could
cause electrical faults and short-circuits.

INFORMATION PLATE

Located on either side of the charger.

EEC DECLARATION OF CONFORMITY

Enersys hereby declares that the chargers in the
Powertech IQ range covered by this declaration 
conform to:

Directive 2006/95/EC:

Low voltage Directive

European Standard:
EN60335-1
EN60335-2-29
EN60950-1

Directive 2004/108/EC:

Electromagnetic compatibility

EN61000-6-2 : 2001
EN61000-6-4 : 2001

Directive 2002/95/EC:

ROHS

Safety and use instructions Powertech IQ - Single phase chargers