  1.   Application

The water refilling system is used to automatically maintain 

the nominal electrolyte levels.

The charging gasses escape through the vent on each cell.

NO WATERING IN THE FIRST 10 CYCLES.

  2.   Function

A valve and a float together control the topping up process 

and maintain the correct water level in each cell. The valve 

allows the flow of water into each cell and the float closes the 

valve when the correct water level has been reached.

For fault-free operation of the water refilling system, please 

note the instructions below:

 2.1  Manual or automatic connection

The battery should be topped up shortly before completion 

of a full charge, as at this point the battery has reached a 

defined operational state resulting in satisfactory electrolyte 

circulation. Filling takes place when   the  connector  (7)  from 

the tank is connected to the coupling (6) on the battery.

Manual or automatic coupling has to be done in the intervals 

according point 7. (see point 7.)

 2.2  Filling time

Filling time depends on the utilisation rate and the 

corresponding battery temperature. Generally speaking, the 

top up process takes a few  minutes and can vary according to 

the battery range; after this, if manual filling is being used, the 

water supply to the battery should be turned off.

 2.3  Working pressure

The water refilling system should be installed in such a way 

that a water pressure of 0.2 to 0.6 bar is obtained (with at 

least 2 m height difference between the upper edge of the 

battery and the lower edge of the tank). Any deviation from 

this means that the system will not function properly.

 2.4  Purity

The topping up water must be purified.  The water used to 

refill the batteries must have a conductance of not more 

than 30 µS/ cm. The tank and pipes must be cleaned before 

operating the system.

 2.5  Pipe system on the battery

The pipe system to the individual battery cells must follow 

the battery’s electrical circuit. This reduces the risk of 

current leakage in the presence of electrolytic gas causing 

an explosion (EN 62485-3). A maximum of 18 cells may be 

connected in a series.

The system should not be modified in any way.

 2.6  Working temperature

In winter, batteries fitted with Aqualevel should only be 

charged or refilled in a room temperature above 0 °C.

 2.7  Flow control

A flow indicator built into the water supply pipe to the battery 

monitors the filling process. During filling the water flow 

causes the built-in disc in the flow indicator to turn.  When all 

the plugs are closed the disc stops, indicating that the filling 

process is complete.

  6.   Malfunctions

If malfunctions are found on the battery or the charger, our 

service department should be called in without delay. The 

measurements taken in point 3.3 will facilitate fault finding 

and their elimination.

A service contract with us will make it easier to detect and 

correct faults in good time.

 7.  Water topping up interval

STANDARD AND OPTIONAL EQuIPMENT

Water Less

Water Less 20

Aqualevel

Airmix

Wi-iQ

®

Blinky

 1)

 Standard 

 

Option 

 not available

1)

  batteries with 2 and 3 positive plates are supplied with Blinky, not with Wi-iQ as standard

Water Less

®

 variant

Water toping up intervals

Battery

Charger

Charge factor

1 shift operation

3 shift operation

Water Less

50 Hz

1.20

20 cycles (4 weeks)

20 cycles (2 weeks)

Water Less

HF

1.10

40 cycles (8 weeks)

40 cycles (5 weeks)

Water Less Airmix

HF

1.07

65 cycles (13 weeks)

65 cycles (8 weeks)

Water Less 20

HF/50 Hz

1.04

100 cycles (20 weeks)

100 cycles (12 weeks)

Aqualevel - Water refilling system (optional accessory)