background image

Temperature (°C/°F)

10/50

15/59

20/68

25/77

30/86

35/95

40/104

Recommended

2.33

2.31

2.29

2.27

2.25

2.23

2.21

Minimum

2.31

2.29

2.27

2.25

2.23

2.21

2.21

4. Installation

Install in a clean and dry area. DataSafe

®

 XE batteries release minimal 

amounts of gas during normal operation (gas recombination efficiency  

≥ 95%). They can be installed near the main equipment. Batteries must  

be installed in accordance with local, national and international regulations 

and manufacturer’s instructions.

n

 Temperature

Avoid placing the battery in areas of high temperature or in direct sunlight. 

The battery will give the best performance and service life when working at 

a temperature between 20˚C (68˚F) and 25˚C (77˚F). The maximum operating 

temperature range is -40˚C (-40˚F) to +50˚C (+113˚F).

n

 Ventilation

Under normal conditions gas release is very low and natural ventilation 

is sufficient for cooling purposes and inadvertent overcharge, enabling 

DataSafe XE batteries to be used safely in offices and with main equipment. 

However care must be taken to ensure adequate ventilation when placed  

in cabinets. Batteries must not be placed in sealed cabinets.

n

 Security

All installation and ventilation must comply with the current local, national 

and international regulations. 

n

 Mounting

Battery racks or cabinets, supplied by EnerSys

®

, are recommended for 

proper installation. Assemble the rack according to instructions. Place the 

monoblocs on the rack and arrange the positive and the negative terminals 

for connection according to the wiring diagram. Check that all contact 

surfaces are clean and apply the bloc connectors and the terminal screws. 

Tighten the screws securely. Follow the polarity to avoid short circuiting  

of blocs. Finally connect the battery terminals. It is important that the battery 

is mounted firmly.

n

 Installation of High Voltage Batteries

A battery consisting of 10 or more blocs connected in series presents 

additional hazards and the following notes on installation should be 

employed.

•  During installation process, limit the battery voltage by omitting  

inter-bloc connectors to give a maximum section voltage of 120V  

or 10 blocs.

•  The omitted inter-bloc connectors should be chosen such that they  

are in an easily accessible position. These connectors should only 

be fitted with the load and charger isolated and when the rest of the 

installation is complete.

•  Never work alone on high voltage batteries.
•  Always use insulated tools and wear approved high voltage insulating 

gloves.

•  When supplied, fit the “high voltage battery” warning labels in  

a prominent position.

n

 Torque

Tighten the nuts or bolts to the recommended levels of fastening torque 

indicated on the product label (if applicable). A loose connector can cause 

problems in charger adjustment, erratic battery performance, possible 

damage to the battery and/or personal injury.

n

 Blocs in Parallel Strings

When using constant voltage chargers, ensure that the connections 

between the charger and the end of each string within the battery have the 

same electrical resistance. Parallel strings should be limited to five strings.

5. Operation

5.1. Float Voltage

Constant voltage chargers are recommended. The charging voltage should 

be set at the equivalent of 2.29Vpc at 20˚C (68˚F) or 2.27Vpc at 25˚C (77˚F). 

The minimum charging voltage, at any temperature, is 2.21Vpc.  

The recommended float voltage temperature compensation is as follows:

5.2. Charging Current

Due to the very low internal resistance DataSafe XE monoblocs will accept 

very high current during recharge and there is not a need to limit the 

available current. For cost and practicle purposes in float applications  

where recharge time to repeat duty is not critical, the rectifier current  

can be limited to the load plus 0.1C

10

 Amps.

5.3. Fast Recharge

In instances where the time to repeat duty is critical the charge voltage 

should be set to 2.40Vpc at 20˚C (68˚F), with the rectifier current limit set to 

a minimum of 0.1C

10

 A. Fast charge should be stopped and reverted to float 

voltage after approximately 10 to 15 hours.

5.4. Periodic Boost Charge

In normal operation a periodic boost charge is not required. However,  

in some cases such as when extended or repeated line power outages 

result in the battery exeriencing extended periods of undercharging,  

a boost charge equivalent to 2.40Vpc at 20˚C (68˚F) for a maximum  

of 15 hours can be applied.

5.5. Discharging

For maximum battery life, the end of discharge voltage should be limited  

to 1.60Vpc for low rate discharges or 1.50Vpc for high rate discharges 

(10 minutes or less in rated duration). Failure to protect batteries from 

discharges exceeding this level may impact warranty.

n

 Discharged Monoblocs

DataSafe XE batteries must not be left in a discharged condition after 

supplying the load, but must be immediately returned to float recharge 

mode. Failure to observe these conditions may result in greatly reduced 

service life and unreliability.

n

 Accidental Deep Discharge

When the battery is completely discharged, the sulphuric acid is completely 

absorbed and the remaining electrolyte consists only of water. At this point, 

the sulphation of the plates is at its maximum, considerably increasing the 

cell’s internal resistance.

Important notice

: this type of deep discharge will provoke a premature 

deterioration of the battery and a noticeable effect on life expectancy.

6. Maintenance and Records

In practice, the user usually specifies the maintenance schedule based on 

site criticality, location and manpower.

However, the following may be used as a suggested maintenance schedule.

•  Monthly (record all readings)

Measure the battery string voltage. If necessary, adjust the float voltage to 

the correct value.

•  Every six months (record all readings)

–  Measure the battery string voltage. If necessary, adjust the float 

voltage to the correct value.

–  Measure individual bloc voltages.
–  Bloc to bloc connection resistance (Ohms)
–  Terminal Connection Resistance (Ohms)
–  Ambient temperature in the immediate environment
–  Check the fastening torque indicated on the product label

Inspect for contamination by dust, loose or corroded connections. If necessary, 

isolate the string/bloc and clean with a damp soft cloth. Warning: Do NOT 

use any type of oil, solvent, detergent, petroleum-based solvent or ammonia 

solution to clean the battery containers or lids. These materials will cause 

permanent damage to the battery container and lid and will invalidate the 

warranty.
Keep a logbook to record values, power outages, discharge tests, etc.
An autonomy check can be carried out once or twice a year.
The above record taking is the absolute minimum to protect the warranty.
This data will be required for any warranty claim made on the battery.
Contact EnerSys if you have any questions regarding maintenance.

7. Disposal

DataSafe XE batteries are recyclable. Scrap batteries must be packaged 

and transported in accordance with prevailing transportation rules and 

regulations.
Scrap batteries must be disposed of in compliance with local and national 

laws by a licensed or certified lead acid battery recycler.

Due to the phenomena of gas recombination, it is not uncommon to note  

a variation in individual block float voltages of 2% (or up to 5% for 

relatively new batteries). However the total voltage of the battery shall  

be within the limits stated above.

Reviews: