TESTING AND FAULT ISOLATION
1.
U
General
This section contains battery functional tests and fault isolation information. Trouble
shooting is presented in chart form (Ref. Fig.8).
2.
U
Required Test Equipment (Ref. Fig. 4)
U
.
U
NOTE:
U
Test equipment having equivalent specifications can be used.
NOMENCLATURE MFR MODEL/PN
APPLICATION
DC Power Supply, Mead Testing/F1
regulated, 40V dc
@ 10A minimum with
Blocking Diode on Power
Supply or Analyser.
(this can be replaced by
the following
Charger/Analyser) Mead
Charger/ Analyser Testing/F1
DC Fluke
Fluke
85
Testing/F1
Voltmeter, precision
(
0.5%) 0 to 50V
Discharge unit
Digatron RCT
50-24 Testing/F1
Capable of 5,10 & 30
Amp discharge.
Required Test Equipment
Figure 4
Page 7