6.0 Data Management, continued
53
704-939-B10-001 Rev. A5 (06/2019)
The following table displays the various analog alarms with common settings for the DM3X.
Table 6-3, Recommended Settings for DM3X Analog Alarms
Analog Alarms and Common Settings
Analog Alarms
Description
Alarm
Enable
LOLO
LO
HI
HIHI
Deadband
psTotalStringVoltage
36V Scaled representation of the full
battery string in 1/100 Volts units
0x0F
3300
3500
4520
4570
50
Individual Battery Voltage
Battery Voltage of 12V Battery in
1/100 Volts units
0x0F
1050
1150
1530
1550
20
psInputVoltage
120V
Scaled representation of the input
line voltage in 1/100 Volts units
0x0F
Varies by site. The XM2 will switch to standby at
n15% / -30%
220V
0x0F
psRMSCurrentIn
Scaled representation of the Power
Supply’s RMS current in 1/100 A
units
0x00
Set as desired per site
psPowerIn
Representation of the Power
Supply’s input power in 1 W units
0x00
Set as desired per site
psFrequencyOut
Representation of Power Supply’s
output frequency in 1/100 Hz units
0x00
Set as desired per site
psOutputVoltage
Scaled representation of the Power
Supply output voltage in 1/100 Volts
units
0x0F
4300
4550
5050
5300
200
0x0F
5650
6000
6600
7000
200
0x0F
7800
8200
9150
9300
200
psPowerOut
Representation of Power Supply
output power in 1W units
0x00
It is recommended that psOutputCurrent be used for
output alarms.
psStringChargeCurrent
Battery string charge current, scaled
in 1/100 Amp units
0x0C
Disable
Disable
1200
1250
20
psStringDischargeCurrent
Scaled representation of battery
string discharge current. This is an
RMS value in 1/100 Amps
0x00
Set as desired per site
psStringFloat
Battery string float charge current,
scaled in 1/100 Amp units
0x0C
Disable
Disable
1200
1250
20
psOutputCurrent
15A Scaled representation of Power
Supply RMS current in 1/100 Amp
units
0x0C
Disable
Disable
1650
1720
20
18A
0x0C
Disable
Disable
1980
2060
20
psTemperature
-40 to +80 degrees C
0x0F
Varies by Site
docsIfDownChannelPower
The CM’s receive RF power scaled
in 1/10 dBmV units
0x0F
-150
-10
10
150
15
docsIfCmStatusTxPower
The CM’s transmit RF power scaled
in 1/10 dBmV units
0x0C
0
0
500
550
15
atiBBsysViewTimeInStandby
Time in seconds that the Power
Supply’s inverter is currently running
due to outage or self-test
0x0C
0
0
Set as desired
for notification of
extended outage
10
Alarms for Optional Generator
GenVBatIgnition
Scaled representation of the
generator’s ignition battery in 1/100
Volts
0x0F
1150
1200
1500
1550
20
genEnclosureTemperature
Temperature inside generator’s
enclosure in degrees C
0x09
-40
0
0
55
5