Operating Instructions 

01825E 

output until they have been discharged a 
number of times. 

5. Do not excessively discharge batteries. 

 

Excessive discharge can cause polarity 
reversal of individual cells resulting in 
complete failure shortly thereafter.  Limited 
use of new batteries will minimize the chance 
of cell reversal. 

6.  CHECK THE LEVEL OF THE ELECTROLYTE 

IN CONVENTIONAL LIQUID ELECTROLYTE 

ACID BATTERIES MONTHLY.  MAINTAIN 
THE PROPER ELECTROLYTE LEVEL BY 
ADDING DISTILLED OR PURIFIED WATER 
WHEN NECESSARY.  Electrolyte levels lower 
during discharge and rise during charge.  
Therefore, it is mandatory that water be added 
to cells ONLY when they are fully charged; do 
not overfill.  Old batteries require more 
frequent additions of water than do new 
batteries. 