[0203072TSS] TSS-D Battery Chargers r1
User's Manual
AC INPUT CONNECTION AND VOLTAGE SETTINGS
The charger must be connected to the AC input using an adequate cable and plug, with
disconnect switch and fuses.
AC VOLTAGE SELECTION 1 x 208/220/240V
•
Find the POWER TRANSFORMER TAPS and the label with the list of the NOMINAL
voltages available.
POSITION
240/208 VAC
INPUT
1
240 VAC
2
220VAC
3
208 VAC
•
Using an adequate AC-voltmeter, measure the value of the REAL AC input voltage
available at the mounting location of the charger.
•
Identify which of the 3 NOMINAL voltage values is closest to the REAL measured value.
Example 1:
if the measured voltage is 210 VAC, the transformer should be
connected to the tap that corresponds to 208 VAC.
Example 2:
if the measured voltage is 235 VAC, the transformer should be
connected to the tap that corresponds to 240 VAC.
•
Move the transformer wires marked with the letter “A” to the correspondent terminal
blocks.
__________________________________________________________________________________________________________________________________________________
Page 7/19
ATTENTION!
The proper setting of the power transformer taps is fundamental
for the correct operation of the charger.
If the real AC input voltage is different than the AC nominal voltage to which the charger is set,
the charging current of the charger may be significantly different than the nominal.