5
Special fittings / using accessories
FI protection switch
5.1
The FI circuit breaker option can only be supplied by the fac-
tory.
The FI circuit breaker (RCD) is a protective measure against
dangerous body currents according to DIN VDE 0100-551.
1.
The assembly's earthing connection clamps must be
connected to the earthing spike by at least 16mm² of
earthing cable (green/yellow). The spike must be driven
into the ground. BG Bau recommends an earthing re-
sistance of ≤ 50Ω (see BGI 867).
2.
Alternatively, a proper earthing device conforming to
VDE 0100-540 can be used (such as the main earthing
line in buildings).
WARNING!
The generator must be earthed.
In this special case the generator must be earthed! The
above-mentioned safety warnings with other wording are
not relevant for this special fitting.
1.
The effectiveness of this protective measure must be
checked at least once a month by an electrical expert or,
if suitable measuring and testing devices are available,
by an electrotechnically trained person under the guid-
ance and supervision of an electrical expert.
2.
Additionally, every work day, the user must check the
mechanical operation of the release by activating the test
button on the residual current protection device (RCD)
(seeFig. 5-1 -10))
.
Earthing requirements:
Attention!
Summary of Contents for ESE 1107 DBG DIN
Page 10: ...General information 10 ESE 807 1107 1307 1407 DBG ES DIN Status at February 2013 Notes ...
Page 25: ...Status at February 2013 ESE 807 1107 1307 1407 DBG ES DIN 25 Notes ...
Page 32: ...32 ESE 807 1107 1307 1407 DBG ES DIN Status at February 2013 Notes ...
Page 47: ...Status at February 2013 ESE 807 1107 1307 1407 DBG ES DIN 47 Notes ...
Page 72: ...72 ESE 807 1107 1307 1407 DBG ES DIN Status at February 2013 Notes ...
Page 77: ...Status at February 2013 ESE 807 1107 1307 1407 DBG ES DIN 77 Notes ...