Description of device parameters
Waterpilot FMX21
98
Hauser
Write permission
Operator/Maintenance/Expert
Description
Enter the pressure value for the lower calibration point (vessel empty). See also "Empty
calib.".
Prerequisite
• "Level selection" = In pressure
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting
0.0
Empty height
Write permission
Operator/Maintenance/Expert
Description
Enter the height value for the lower calibration point (vessel empty). The unit is selected
via the "Height unit" parameter.
Prerequisite
• "Level selection" = In height
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting
0.0
Full calib.
Write permission
Operator/Maintenance/Expert
Description
Enter the output value for the upper calibration point (vessel full). The unit defined in
"Output unit" must be used.
Note
• In the case of wet calibration, the level (e.g. vessel full or partially filled) must actually be
available. The associated pressure is then automatically recorded by the device.
• In the case of dry calibration, the level (vessel full) does not have to be available. For the
"In pressure" level selection, the associated pressure must be entered in the "Full pressure"
parameter. The associated height has to be entered in the "Full height" parameter for the
"In height" level selection.
Factory setting
100.0
Full pressure
Write permission
Operator/Maintenance/Expert
Description
Enter the pressure value for the upper calibration point (vessel full). See also "Full calib.".
Summary of Contents for Waterpilot FMX21