Description of device parameters
Waterpilot FMX21
94
Hauser
14.6 Expert → Measurement → Pressure
Set LRV
Write permission
Operators/Service engineers/Expert
Description
Set the pressure value, level or content for the lower current value (4 mA).
Factory setting
• 0.0 % in Level measuring mode
• 0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode
Set URV
Write permission
Operators/Service engineers/Expert
Description
Set the pressure value, level or content for the upper current value (20 mA).
Factory setting
• 100.0 % in Level measuring mode
• URL Sensor or according to ordering information in Pressure measuring mode
Meas. pressure
Write permission
No write permissions. Parameter is read only.
Description
Displays the measured pressure after sensor trim, position adjustment and damping.
Pressure simulation value →
→ Pressure →
↓
↑
↓
Sensor
→
Sensor trim
→
Position
adjustment
→
Damping
→
Electr. Delta P
→
P
→
Level
→
I
→
Current output
↓
↓
↓
↓
Sensor pressure
Corrected
press.
Corrected
Damping
Pressure
pressure
Sensor pressure
Write permission
No write permissions. Parameter is read only.
Description
Displays the measured pressure before the sensor trim.