Waterpilot FMX21
Commissioning
Hauser
65
Description
Selection of data packages for up/download function in Fieldcare and PDM.
Prerequisite
DIP switch set to "SW" and "Damping" set to "on". If you download using the factory setting
"Configuration copy", all parameters required for a measurement will be downloaded. The
functionality of the "Electronics replace" setting is reserved for Hauser Service and
can be accessed only if the correct device access code is entered.
Options
• Configuration copy: This option overwrites general configuration parameters with the
exception of the serial number, order number, calibration, position adjustment,
application and tag information.
• Device replacement: This option overwrites general configuration parameters with the
exception of the serial number, order number, calibration and position adjustment.
• Electronics replace: This option overwrites general configuration parameters.
Factory setting
Configuration copy
9.14 Operation and settings via RIA15
1
2
3
4
5
6
7
8
A0017719
7
Display and operating elements of the process indicator
1
Symbol: operating menu disabled
2
Symbol: error
3
Symbol: warning
4
Symbol: HART communication active
5
Operating keys "-", "+", "E"
6
14-segment display for unit/TAG
7
Bar graph with indicators for under range and over range
8
5-digit 7-segment display for measured value, digit height 17 mm (0.67 in)
The device is operated using three operating keys on the front of the housing. The device
setup can be disabled with a 4-digit user code. If the setup is disabled, a padlock symbol
appears on the display when an operating parameter is selected.
Enter key; for calling up the operating menu, confirming the selection/configuration of
parameters in the operating menu
,
Selecting and setting/changing values in the operating menu; pressing the '-' and '+' keys
simultaneously takes the user back up a menu level. The configured value is not saved.