Commissioning
Waterpilot FMX21
52
Hauser
1000 l
0 l
4 m
r
= 1
g
cm
3
A0018827
1
See steps 10 and 11
2
See steps 13 and 14
3
See step 12
A
h
p
g
=
×
r
r =
1
g
cm
3
B
D
C
E
V
[l]
h
[m]
1000
0
0
4
A0017666
A
See step 12
B
See step 8
C
See step 9
D
See step 10
E
See step 11
F
G
I
[mA]
V
[l]
20
4
0
1000
A0031067
F
See step 13
G
See step 14
1. Select the "Level" measuring mode via the "Measuring mode" parameter.
Menu path: Setup → Measuring mode
L
WARNING
Changing the measuring mode affects the span (URV)
This situation can result in product overflow.
‣
If the measuring mode is changed, the setting for the span (URV) must be checked in
the "Setup" operating menu and readjusted if necessary.
2. Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example.
Menu path: Setup → Press. eng. unit
3. Select the "In height" level mode via the "Level selection" parameter.
Menu path: Setup → Extended setup → Level → Level selection.
4. If density correction is required, assign the temperature probe in the "Auto dens. corr."
parameter.
Menu path: Setup → Extended setup → Level → Level selection.
5. Select a volume unit via the "Output unit" parameter, here "l" (liters) for example. A
density correction is only possible for water. A temperature-density curve that is
saved in the device is used. For this reason, the "Adjust density" (step 12) and "Process
density" (step 15) parameters are not used here.
Menu path: Setup → Extended setup → Level → Output unit
6. Select a volume unit via the "Output unit" parameter, here "l" (liters) for example.
Menu path: Setup → Extended setup → Level → Output unit
7. Select a level unit via the "Height unit" parameter, here "m" for example.
Menu path: Setup → Extended setup → Level → Height unit
8. Select the "Dry" option via the "Calibration mode" parameter.
Menu path: Setup → Extended setup → Level → Calibration mode
9. Enter the volume value for the lower calibration point via the "Empty calib."
parameter, here 0 liters for example.
Menu path: Setup → Extended setup → Level → Empty calib.
10. Enter the height value for the lower calibration point via the "Empty height"
parameter, here 0 m for example.
Menu path: Setup → Extended setup → Level → Empty height