Waterpilot FMX21
Commissioning
Hauser
43
Navigation
Setup → Measuring mode
Write permission
Operator/Maintenance/Expert
Description
Select the measuring mode.
The operating menu is structured differently depending on the measuring mode selected.
Options
• Pressure
• Level
Factory setting
Level
9.5
Selecting the pressure engineering unit
Press. eng. unit
Navigation
Setup → Press. eng. unit
Write permission
Operator/Maintenance/Expert
Description
Select the pressure unit. If a new pressure unit is selected, all pressure-specific parameters
are converted and displayed with the new unit.
Options
• mbar, bar
• mmH2O, mH2O, inH2O
• ftH2O
• Pa, kPa, MPa
• psi
• mmHg, inHg
• kgf/cm
2
Factory setting
mbar or bar depending on the nominal measuring range of the sensor module, or as per
order specifications.
9.6
Position adjustment
A pressure shift resulting from the orientation of the device can be corrected by the
position adjustment.
Pos. zero adjust (gauge pressure sensor)
Navigation
Setup → Pos. zero adjust
Write permission
Operator/Maintenance/Expert
Description
Pos. zero adjustment – the pressure difference between zero (set point) and the measured
pressure need not be known.