Waterpilot FMX21
Description of device parameters
Hauser
111
Write permission
Service engineers/Expert
Description
Use this function to enter the address via which a data exchange is to take place via HART
protocol. (HART 5.0 master: Range 0 to 15, where address = 0 calls up the "Signaling"
setting; HART 6.0 master: Range 0 to 63)
Factory setting
0
Preamble number
Write permission
Service engineers/Expert
Description
Use this function to enter the number of preambles in the HART protocol.
(Synchronization of the modem components along a transmission path, each modem
component could "swallow" one byte, at least 2 bytes must be the preamble.)
Input range
2...20
Factory setting
5