TTR31, TTR35
Operation
Hauser
19
5.1.6
Settings for output - 1x switch output and 1x analog output (4 to 20 mA)
Output 1
.
Output 2,
as option
.
Switch-back point
value
,M,
Switch-back point
-50 to 149 °C
(-58 to 300 °F)
in increments of 0.1 °C
(0.18 °F)
.
Switch point delay
,M,
Delay time
0...99 s
in increments of 0.1 s
Factory setting:
0 s
.
Switch-back point
delay
,M,
Delay time 0...99 s
in increments of 0.1 s
Factory setting:
0 s
Min. distance between SP and RSP: 0.5 °C/K (0.9 °F)
Function
group
Function
Settings
Description
Output 1
.
Output 2,
as option
6
6.
Switching
characteristic
0>.,
WINC:
window/NC contact
HYNC:
hysteresis/NC contact
WINO:
window/NO contact
HYNO:
hysteresis/NO contact
4 - 20: analog output
Factory setting:
HYNO
.
Switch point value
,M,
Switch point
-49.5 to 150 °C
(-57.1 to 302 °F)
in increments of 0.1 °C
(0.18 °F)
Function
group
Function
Settings
Description