Overfill Prevention System SOP600
6
Hauser
• Two closing contacts per tank. Protected by 2A fuses (replaceable)
• Min. current/voltage: 10 mA 10 V
• Max. current/voltage:
– UL: C 300
– AC-15: 1.5 A 250 V
AC
– DC-13: 2 A 24 V
DC
(0.1 Hz)
Surge voltage resistance
2
500 V
Overvoltage category
(VDE 0110-1)
III
Power supply
Supply voltage
Voltage
range
90 to 132 V
AC
(100 to 120 V auto-select input)
180 to 264 V
AC
(200 to 240 V auto-select input)
Power
supply
frequency
50 to 60 Hz(+/- 6%)
Power
consumption
Depends on the type of Overfill Prevention System (AOPS, MOPS, SIL2, SIL3, options used etc.) and
the number of tanks
Max. at 230 V: 3 A
Max. at 115 V: 5 A
Max. back-
up fuse
16 A, tripping characteristic C
Electrical connection
Terminal strip (in cabinet, cable run from below)
Environment
Control cabinet:
Indoor installation (max. 25 °C), non-hazardous area
External text display unit:
Only indoors, non-hazardous area