Soliwave FDR16/FQR16
Hauser
39
Technical data
13�4�3 Degree of protection
•
.
: IP69
•
-
: IP67
13�4�4 Vibration resistance
• Vibration according to EN 60068-2-6
•
Excitation: Sine
•
Frequency range: 5 to 500 Hz
•
Amplitude: 5 to 15 Hz (5.5 mm) peak / 15 to 500 Hz 5 g
•
Passing speed: 1 octave per minute
•
Test directions: 3 directions (X, Y, Z)
•
Test duration: approx. 140 minutes per direction (approx. 70 minutes per temperature/
direction)
•
Test temperature: -40 to +70 °C
13.4.5
Shock resistance
• Shock according to EN 60068-2-27
•
Excitation: half sine
•
Shock duration: 18 ms
•
Amplitude: 30 g
•
Number of shocks: 3 per direction and temperature
•
Test directions: 6 directions (±X, ±Y, ±Z)
•
Test temperature: -40 to +70 °C
13�4�6 Electromagnetic compatibility
• Interference emission to EN 61326, Electrical Equipment Class B
• Interference immunity to EN 61326, Appendix A (Industrial)
13.5
Process
13.5.1
Process temperature
•
-20 to +60 °C (-4 to +140 °F)
•
-20 to +450 °C (-4 to +842 °F) with optional high temperature adapter
•
Observe deviating temperature ranges for the accessories offered!
13.5.2
Process pressure
• 0.5 to 6.8 bar (7 to 99 psi) absolute, only to be observed for direct process mounting
• 0.8 to 5.1 bar (12 to 74 psi) absolute, when using the optional high temperature adap-
ter
• 0.5 to 21 bar (7 to 305 psi) absolute, when using the optional high pressure adapter
•
Observe deviating pressure ranges for the accessories offered!