Appendix
RMA42
58
Hauser
11.4
Diagnostics menu
11.5
Expert menu
In addition to all the parameters in the Setup menu, the following parameters are also available in
the Expert mode:
Function
Min
Max
Gradient
Inband
Outband
Function of the relay
Setpoint
Numerical value
1)
0
Switching threshold for relay
Setpoint 2
Numerical value
1)
0
Second switching threshold for relay
Only for the inband and outband functions.
Time base
Only visible if "Function"
= "Gradient" was set
0-60
0
Time base for gradient calculation in seconds
Hysteresis
Numerical value
1)
0
Hysteresis for switching threshold(s)
System
Access code
0000 to 9999
0000
User code to protect the device configuration.
0000 = protection through user code disabled
Overfill protect
No
Yes
If the device is used for overfill protection (see Section 6.4.8), "Yes" must be
selected for "Overfill protect".
Reset
No
Yes
Resets the device to the order configuration
Setup menu
1) Numerical values consist of 6 digits where the decimal point counts as a digit, e.g. +99.999
Diagnostics menu
Current diagn
Error code
Displays the error code currently present
Last diagn
Error code
Displays the last error code
Operating time
Numerical value
Displays the hours operated up until now
Diagnost logbook
Diagnostics x
Displays the last 5 error codes
Device information
Device tag
Displays the device name
i
TAG channel 1
Serial number
Displays the serial number
Order code
Displays the order code
Order identifier
Displays the order number
Firmware version
Displays the firmware version
ENP version
Displays the ENP version
Expert menu
Direct access
4-digit code
System
Save user setup
No
Yes
Select ‘Yes’ to save the current device settings. The device can be reset to
the saved settings by means of ‘Reset’->‘User reset’.
Input
Analog in 1
Bar 0%
Numerical value
1)
0
Configures the 0%-value for the bar
graph
1) Numerical values consist of 6 digits where the decimal point counts as a digit, e.g. +99.999