RLN42
Electrical connection
Hauser
11
6
Electrical connection
6.1
Connection conditions
A flat-blade screwdriver is required to establish an electrical connection to screw or push-
in terminals.
0,5-0,6 Nm
5-7 lb In
7 mm (0,28")
AWG 24-14
0,2 -2,5 mm
5
²
AWG 24-14
0,2 - ,5 mm
5 2
²
10
(0,39")
mm
1.
2.
1.
1.
2.
3.
A0040201
4
Electrical connection using screw terminals (left) and push-in terminals (right)
L
CAUTION
Destruction of parts of the electronics
‣
Switch off power supply before installing or connecting the device.
NOTICE
Destruction or malfunction of parts of the electronics
‣
ESD - Electrostatic discharge. Protect the terminals from electrostatic discharge.
6.1.1
Special connection instructions
• Disconnecting units and auxiliary circuit protective systems with suitable AC or DC
values must be provided in the building installation.
• A switch/power circuit breaker must be provided close to the device and clearly marked
as a disconnecting unit for this device.
• An overcurrent protection unit (I≤16 A) must be provided in the installation.
• The voltages applied at the input are extra-low voltages (ELV). Depending on the
application, the supply and switching voltage at the relay output can be a dangerous
voltage (>30 V). Safe galvanic isolation to the other connections is provided for this
scenario.
For information on the connection data, see the "Technical data" section.