Operating menu
Proservo NMS83
248
Hauser
Additional information
Read access
Operator
Write access
Maintenance
P3 position
Navigation
Setup → Advanced setup → Application → Tank config → Pressure → P3 position
Description
Defines the position of the top pressure transmitter (P3), measured from zero position
(tank bottom or datum plate).
User entry
0 to 100
000 mm
Factory setting
20
000 mm
Additional information
Read access
Operator
Write access
Maintenance
P3 offset
Navigation
Setup → Advanced setup → Application → Tank config → Pressure → P3 offset
Description
Offset for the top pressure (P3). The offset is added to the measured pressure prior to any
tank calculation.
User entry
–2.5 to 2.5 bar
Factory setting
0 bar
Additional information
Read access
Operator
Write access
Maintenance
The offset is added to the measured pressure prior to any tank calculation.
P3 absolute / gauge
Navigation
Setup → Advanced setup → Application → Tank config → Pressure → P3 absolut/
gauge
Description
Defines whether the connected pressure transmitter measures an absolute or a gauge
pressure.
Selection
• Absolute
• Gauge