Operating menu
Proservo NMS83
208
Hauser
The switching state of these relays is defined by the
Output simulation
parameter as
follows:
Output simulation
State of relay 1
State of relay 2
Expected result on the
terminals of the I/O module
Simulating active
Closed
Closed
Closed
Simulating inactive
Open
Open
Open
Fault 1
Closed
Open
Open
Fault 2
Open
Closed
Open
The
Fault 1
and
Fault 2
options can be used to check the correct switching behavior
of the two relays.
Output value
Navigation
Setup → Advanced setup → Input/output → Digital Xx-x → Output values
Prerequisite
Operating mode (→ 205)
Output passive
Description
Shows the digital output value.
Additional information
Read access
Operator
Write access
-
Readback value
Navigation
Setup → Advanced setup → Input/output → Digital Xx-x → Readback value
Prerequisite
Operating mode (→ 205)
Output passive
Description
Shows the value read back from the output.
Additional information
Read access
Operator
Write access
-
Used for SIL
Navigation
Setup → Advanced setup → Input/output → Digital Xx-x → Used for SIL
Prerequisite
Operating mode (→ 205)
Output passive
Description
Determines whether the digital I/O module is in SIL mode.