Commissioning
Proservo NMS83
108
Hauser
4-20mA output
Each Analog I/O module of the device can be configured as a 4...20mA analog output. To
do so, proceed as follows:
1. Navigate to: Setup → Advanced setup → Input/output → Analog I/O
2. Go to the
Operating mode
parameter and select the
4..20mA output
option.
3. Go to the
Analog input source
parameter and select the tank variable which is to be
transmitted via the 4...20mA output.
4. Go to the
0 % value
parameter and enter the value of the selected tank variable
which will be mapped to 4 mA
5. Go to the
100 % value
parameter and enter the value of the selected tank variable
which will be mapped to 20 mA.
The
Analog I/O
submenu contains more parameters which can be used for a more
detailed configuration of the analog output. For a description see → 196
Modbus
The Proservo NMS8x acts as a Modbus slave. Measured or calculated tank values are
stored in registers which can be requested by a Modbus master.
The following submenu is used to configure the communication between the device and
the Modbus master:
Setup → Advanced setup → Communication → Modbus X1-4 →Configuration (→ 216)
V1
The following submenus are used to configure the V1 communication between the device
and the control system:
• Setup → Advanced setup → Communication → V1 X1-4 → Configuration (→ 219)
• Setup → Advanced setup → Communication → V1 X1-4 → V1 input selector (→ 223)