Proline t-mass A 150 HART
Commissioning
Hauser
61
Switch-on value
Switch-off value
(Status)
Assign status
Switch-on delay
Switch-off delay
Failure mode
Switch status
Invert output signal
Parameter overview with brief description
Parameter
Description
Selection/
User entry
Factory setting
Operating mode
Specify the output as a
pulse, frequency or switch
output.
• Pulse
• Frequency
• Switch
Pulse
Assign pulse output
Select the process variable
for the pulse output.
• Off
• Mass flow
• Corrected volume flow
• FAD volume flow
Off
Assign frequency output
Select the process variable
for the frequency output.
• Off
• Mass flow
• Corrected volume flow
• FAD volume flow
• Temperature
Off
Assign switch output
Select the function for the
switch output.
• Off
• On
• Diagnostic behavior
• Limit value
• Status
Off
Assign diagnostic
behavior
Select the diagnostic
behavior for the switch
output.
• Alarm
• Alarm or warning
• Warning
Alarm
Assign limit
Select the process variable
for the limit function.
• Mass flow
• Corrected volume flow
• FAD volume flow
• Totalizer
Mass flow
Assign status
Select the device status for
the switch output.
Low flow cut off
Low flow cut off